York BP 090 Heat Pump User Manual


 
66307-YIM-B-0606
40 Unitary Products Group
FIGURE 24: UNIT CONTROL BOARD
TABLE 38: UNIT CONTROL BOARD FLASH CODES
FLASH CODE DESCRIPTION
GREEN
LED
16
RED
LED
8
RED
LED
4
RED
LED
2
RED
LED
1
On Steady This is a Control Failure - - - - -
1 Flash Not Applicable - - - - -
2 Flashes
Control waiting ASCD
*
Flashing Off Off On Off
3 Flashes HPS1 Compressor Lockout Off Off Off On On
4 Flashes HPS2 Compressor Lockout Off Off On Off Off
5 Flashes LPS1 Compressor Lockout Off Off On Off On
6 Flashes LPS2 Compressor Lockout Off Off On On Off
7 Flashes FS1 Compressor Lockout Off Off On On On
8 Flashes FS2 Compressor Lockout Off On Off Off Off
9 Flashes Ignition Control Locked Out / Ignition Control Failure Off On Off Off On
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
1
Flashing On Off On Off
11 Flashes
Compressors locked out because the Economizer is using free
Cooling
1
Flashing On Off On On
12 Flashes Unit Locked Out due to Fan Overload Switch Failure Off On On Off Off
13 Flashes
Compressor Held Off due to Low Voltage
1
Flashing On On Off On
14 Flashes EEPROM Storage Failure Off On On On Off
OFF No Power or Control Failure Off Off Off Off Off
*.
Non-alarm condition.
Check
Alarm
History
Reset All
ASCDs for
One Cycle
Non Alarm
Condition Green
LED Flashing
Current Alarm
Flashed
Red LED