York BP 090 Heat Pump User Manual


 
66307-YIM-B-0606
18 Unitary Products Group
TABLE 8: ELECTRICAL DATA - 7-1/2 TON HP
Voltage
Compressors
OD
Fan
Motors
Supply Air
BLower
Motor FLA
Pwr
Exh
Motor
Electric Heater
Model No.
Actual
Kw
Heater
Amps
Minimum Circuit
Ampacity (Amps)
MCA
with Power
Exhaust
(Amps)
Max Fuse
Size
*
(Amps)
Max Fuse Size
w/Pwr. Exh.*
(Amps)
RLA
ea
LRA
ea
FLA
ea
1.5 HP
(1.1 kW)
2 HP
(1.5 kW)
FLA
1.5 HP
(1.1 kW)
2 HP
(1.5 kW)
1.5 HP
(1.1 kW)
2 HP
(1.5 kW)
1.5 HP
(1.1 kW)
2 HP
(1.5 kW)
1.5 HP
(1.1 kW)
2 HP
(1.5 kW)
380 8.3 62 1.1 4.3 5.2 2.2
None - - 25.2 26.1 27.4 28.3 30 30 35 35
2TP04520950 5.6 8.5 35.8 36.7 38.0 38.9 40 40 40 45
2TP04521850 11.3 17.2 46.6 47.5 48.8 49.7 50 50 50 50
2TP04522450 15.0 22.8 53.7 54.6 55.9 56.8 60 60 60 60
2TP04523650 21.3 32.4 65.6 66.5 67.8 68.7 70 70 70 70
415 8.3 62 1.1 4.3 5.2 2.2
None - - 25.2 26.1 27.4 28.3 30 30 35 35
2TP04520950 6.7 9.3 36.8 37.7 39.0 39.9 40 40 40 45
2TP04521850 13.5 18.8 48.7 49.6 50.9 51.8 50 50 60 60
2TP04522450 17.9 24.9 56.3 57.2 58.5 59.4 60 60 60 60
2TP04523650 25.4 35.3 69.3 70.2 71.5 72.4 70 80 80 80
*.
Maximum HACR breaker of the same amp size is acceptable.
TABLE 9: ELECTRICAL DATA - 10 TON HP
Voltage
Compressors
OD
Fan
Motors
Supply Air
BLower
Motor FLA
Pwr
Exh
Motor
Electric Heater
Model No.
Actual
Kw
Heater
Amps
Minimum Circuit
Ampacity (Amps)
MCA
with Power
Exhaust
(Amps)
Max Fuse
Size
*
(Amps)
Max Fuse Size
w/Pwr. Exh.*
(Amps)
RLA
ea
LRA
ea
FLA
ea
2 HP
(1.5 kW)
4HP
(3 kW)
FLA
2 HP
(1.5 kW)
4 HP
(3 kW)
2 HP
(1.5 kW)
4 HP
(3 kW)
2 HP
(1.5 kW)
4 HP
(3 kW)
2 HP
(1.5 kW)
4 HP
(3 kW)
380 8.1 73.0 1.1 5.2 7.5 2.2
None -- -- 25.6 27.9 27.8 30.1 30 35 35 35
2TP04521850 11.3 17.2 47.1 49.4 49.3 51.6 50 50 50 60
2TP04522450 15.0 22.8 54.1 56.4 56.3 58.6 60 60 60 60
2TP04523650 21.3 32.4 66.1 68.4 68.3 70.6 70 70 70 80
2HP04535450
33.8 51.4 70.7 73.6 73.4 76.3 80 80 80
80
415 8.1 73.0 1.1 5.2 7.5 2.2
None -- -- 25.6 27.9 27.8 30.1 30 35 35 35
2TP04521850 13.5 18.8 49.1 51.4 51.3 53.6 50 60 60 60
2TP04522450 17.9 24.9 56.8 59.1 59.0 61.3 60 60 60 70
2TP04523650 25.4 35.3 69.8 72.1 72.0 74.3 70 80 80 80
2HP04535450
40.4 56.2 76.8 79.6 79.5 82.4 80 80 80
90
*.
Maximum HACR breaker of the same amp size is acceptable.
†.
Only 25.4 kW of electric heat can be simultaneously energized with the mechanical heating. The full 40.4 kW operates only if both compressors are locked out.