Dimension and
Weights
Table DW-4 – Separated Combustion – Centrifugal Fan Unit Heater Dimensional Data
Model GKND/ GKND/ GKND/ GKND/ GKND/ GKND/ GKND/ GKND/ GKND/ GKND/
GKPD GKPD GKPD GKPD GKPD GKPD GKPD GKPD GKPD GKPD
Unit Size 100 125 150 175 200 225 250 300 350 400
A Height to Top 31.25 31.25 36.25 36.25 36.25 36.25 36.25 36.25 36.25 36.25
Top of Unit (794) (794) (921) (921) (921) (921) (921) (921) (921) (921)
B Height to Top 34.062 34.062 39.062 39.062 39.062 39.062 39.062 39.062 39.062 39.062
Top of Hanger (865) (865) (992) (992) (992) (992) (992) (992) (992) (992)
C Hanging 14.75 17.5 17.5 20.25 23 25.75 28.5 34 39.5 45
Distance Width (375) (445) (445) (514) (584) (654) (724) (864) (1003) (1143)
D Discharge 15.375 18.125 18.125 20.875 23.625 26.375 29.125 34.625 40.125 45.625
Opening Width (391) (460) (460) (530) (600) (670) (740) (879) (1019) (1159)
E Width 17.875 20.625 20.625 23.375 26.125 28.875 31.625 37.125 42.625 48.125
Of Unit (454) (524) (524) (594) (664) (733) (803) (943) (1083) (1222)
F To Centerline 5.875 7.25 7.25 8.625 10 11.25 12.75 15.5 18.25 21
Of Flue (149) (184) (184) (219) (254) (286) (324) (394) (464) (533)
G Hanging 18.5 18.5 18.5 20 20 23 23 23 23 23
Distance Depth (470) (470) (470) (508) (508) (584) (584) (584) (584) (584)
H Depth to 42.75 44.375 44.375 47.187 47.187 50.875 48 50.875 50.875 51
Rear of Housing (1086) (1127) (1127) (1199) (1199) (1292) (1219) (1292) (1292) (1295)
Flue Size (Dia-in.) 4444555666
(Dia-mm) (102) (102) (102) (102) (127) (127) (127) (152) (152) (152)
Blower Size (in) 9 10 10 12 12 12 12 (2) 10 (2) 12 (2) 12
Gas Inlet-Natural Gas (in.) 0.5 0.5 0.5 0.5 0.5 0.75 0.75 0.75 0.75 0.75
Gas Inlet- LP Gas (in.) 0.5 0.5 0.5 0.5 0.5 ½ or ¾½ or ¾½ or ¾½ or ¾½ or ¾
Approx. Shipping wt.
(lb.) 298 330 362 394 426 458 490 558 618 678
(kg) (135) (150) (164) (179) (193) (208) (222) (253) (280) (308)
*The flue openings on all units are 5
1
/8" diameter. Therefore, a transition adaptor is required by installer on these units.
*Canadian units include vent cap and reducer/increaser (if required).
Dimensions in ( ) are in millimeters.
Side View - 100 through 200 Side View - 225 through 400
NOTE: Air intake is round on 225/250
units. For 300/400 units, air intake is
as shown.