Trane UH-PRC002-EN Indoor Fireplace User Manual


 
UH-PRC002-EN20
60° Nozzle
90° Nozzle
“Y” Splitter
Table GD-4 – 60 Degree Nozzle – Approximate Distance of Throw at Nominal Airflow
Distance From
Floor to Bottom Unit Size – Input MBh – (kW)
of Unit “H” 100 125 150 175 200 225 250 300 350 400
ft./(m) (29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
8 75808590 95100110125130138
(2.4) (22.9) (24.4) (25.9) (27.4) (29.0) (30.5) (33.5) (38.1) (39.6) (42.1)
10 65 70 75 79 83 88 95 109 115 120
(3.0) (19.8) (21.3) (22.9) (24.1) (25.3) (26.8) (29.0) (33.2) (35.1) (36.6)
12 60 64 68 72 76 80 84 100 103 108
(3.7) (18.3) (19.8) (20.7) (21.9) (23.2) (24.4) (25.6) (30.5) (31.4) (32.9)
15 50 54 56 61 65 68 71 85 88 94
(4.6) (15.2) (16.5) (17.1) (18.6) (19.8) (20.7) (21.6) (25.9) (26.8) (28.7)
20 NR 49 52 55 59 61 65 77 81 85
(6.1) (14.9) (15.8) (16.8) (18.0) (18.6) (19.8) (23.5) (24.7) (25.9)
Table GD-5 – 90 Degree Nozzles – Approximate Floor Coverage at Nominal Airflow
Distance From Floor to Bottom of Unit “H” – ft./(m)
Unit 10' 15' 20' 25' 30'
Size (3.0) (4.6) (6.1) (7.6) (9.1)
100 NR 30 x 25 NR NR NR
(9.1 x 7.6)
125 NR 35 x 30 NR NR NR
(10.7 x 9.1)
150 NR 40 x 35 NR NR NR
(12.2 x 10.7)
175 NR 45 x 40 NR NR NR
(13.7 x 12.2)
200 NR 50 x 40 40 x 35 NR NR
(15.2 x 12.2) (12.2 x 10.7)
225 NR 55 x 40 48 x 35 NR NR
(16.8 x 12.2) (14.6 x 10.7)
250 NR 60 x 45 56 x 40 50 x 35 NR
(18.3 x 13.7) (17.1 x 12.2) (15.2 x 10.7)
300 NR 70 x 45 65 x 40 60 x 35 55 x 35
(21.3 x 13.7) (19.8 x 12.2) (18.3 x 10.7) (16.8 x 10.7)
350 NR 80 x 50 70 x 45 65 x 40 60 x 35
(24.4 x 15.2) (21.3 x 13.7) (19.8 x 12.2) (18.3 x 10.7)
400 NR 100 x 50 80 x 45 75 x 40 65 x 40
(30.5 x 15.2) (24.4 x 13.7) (22.9 x 12.2) (19.8 x 12.2)
Table GD-6 – “Y” Splitters – Approximate Distance of Throw at Nominal Airflow
Distance From
Floor to Bottom Unit Size – Input MBh – (kW)
of Unit “H” 100 125 150 175 200 225 250 300 350 400
ft./(m) (29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
8 47516065 70728095100103
(2.4) (14.3) (15.5) (18.3) (19.8) (21.3) (21.9) (24.4) (29.0) (30.5) (31.4)
10 41 44 52 56 61 63 69 82 87 92
(3.0) (12.5) (13.4) (15.8) (17.1) (18.6) (19.2) (21.0) (25.0) (26.5) (28.0)
12 37 40 47 51 55 57 63 75 79 82
(3.7) (11.3) (12.2) (14.3) (15.5) (16.8) (17.4) (19.2) (22.9) (24.1) (25.0)
NR = Not Recommended
Notes:
1. All throw data figures are approximate.
2. NR = not recommended at these mounting heights.
3. Nozzles are not available on units below size 100 MBh.
4. Nozzles are available for High Efficiency units. Specify High Efficiency when ordering due to difference in nozzle
configuration.
General
Data