Trane TWE050A-TWE200B Heat Pump User Manual


 
27SS-PRC003-EN
Performance
Data System
Table PD-15 Gross Cooling Capacities (MBh) TTA200B Condensing Unit with TWE200B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 201.0 158.5 221.1 132.8 242.4 89.9 193.1 154.4 212.5 129.3 232.6 86.5 184.9 150.2 203.5 125.7 222.1 83.0 176.4 145.8 194.2 122.0 211.7 79.5
80 202.2 184.9 221.6 152.5 243.5 118.4 194.5 180.9 213.1 148.6 234.1 114.8 186.6 176.8 204.3 144.5 224.2 111.1 178.4 172.6 195.1 140.3 214.1 107.4
6000
85 206.7 206.7 222.8 178.8 244.6 146.0 200.1 200.1 214.3 174.8 235.3 142.4 193.3 193.3 205.5 170.7 225.5 138.8 186.1 186.1 196.4 166.6 215.5 135.1
90 217.1 217.1 224.1 205.3 245.0 172.1 210.4 210.4 215.9 201.5 235.7 168.2 203.4 203.4 207.3 197.5 226.1 164.2 196.1 196.1 198.7 193.5 216.2 160.2
75 204.9 165.7 225.2 130.5 246.0 91.4 196.8 161.6 216.3 126.8 235.8 87.9 188.4 157.3 207.0 123.0 225.4 84.3 179.6 152.9 197.4 119.1 214.5 80.7
80 206.6 194.8 225.8 159.1 247.6 122.3 198.8 190.8 217.0 155.1 237.8 118.8 190.7 186.6 207.9 150.9 227.7 115.1 182.5 182.4 198.5 146.6 217.2 111.3
6675
85 213.4 213.4 227.0 187.8 248.8 152.5 206.6 206.6 218.2 183.8 239.1 148.9 199.4 199.4 209.1 179.7 228.3 143.9 191.9 191.9 199.8 175.5 218.1 139.7
90 224.4 224.4 228.9 217.1 249.3 180.5 217.3 217.3 220.5 213.2 239.7 176.6 210.0 210.0 211.9 209.2 229.8 172.5 202.3 202.3 202.5 202.5 219.6 168.4
75 208.3 172.6 228.5 134.9 248.9 93.0 200.0 168.4 219.3 131.2 238.5 89.5 191.3 164.0 209.8 127.3 227.8 85.8 182.3 159.5 199.1 121.9 216.7 82.0
80 210.6 204.3 229.3 165.4 250.9 126.1 202.7 200.3 220.3 161.3 240.9 122.5 193.9 193.9 210.9 157.0 230.5 118.8 186.3 186.3 201.3 152.7 219.8 115.0
7350
85 219.4 219.4 230.5 196.5 251.4 157.5 212.2 212.2 221.6 192.5 241.6 153.5 204.7 204.7 212.3 188.3 231.4 149.4 197.0 197.0 202.9 184.0 220.9 145.1
90 230.7 230.7 233.3 228.5 252.9 188.5 223.3 223.3 224.9 224.6 243.1 184.5 215.7 215.7 215.9 215.9 232.9 180.4 207.7 207.7 207.9 207.9 222.4 176.2
75 211.2 179.2 231.3 139.1 251.4 94.4 202.6 174.9 221.0 134.2 240.8 90.7 193.8 170.5 211.3 129.8 229.8 86.9 184.7 166.0 201.4 125.3 218.4 83.1
80 214.3 213.5 232.3 171.4 253.7 129.7 205.8 205.8 223.1 167.2 243.4 126.1 198.3 198.3 213.5 162.9 232.8 122.4 190.4 190.4 203.7 158.5 221.9 118.6
8025
85 224.6 224.6 233.7 204.9 254.5 162.9 217.2 217.2 224.6 200.8 244.4 158.8 209.4 209.4 215.2 196.6 234.0 154.6 201.4 201.4 205.6 192.3 223.3 150.3
90 236.3 236.3 236.5 236.5 256.0 196.3 228.6 228.6 228.8 228.8 245.9 192.2 220.7 220.7 220.9 220.9 235.5 188.1 212.4 212.4 212.6 212.6 224.8 183.8
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-15 Gross Cooling Capacities (MBh) TTA200B Condensing Unit with TWE200B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 58.8 46.4 64.7 38.9 71.0 26.3 56.5 45.2 62.2 37.9 68.1 25.3 54.1 44.0 59.6 36.8 65.0 24.3 51.6 42.7 56.9 35.7 62.0 23.3
27 59.2 54.1 64.9 44.7 71.3 34.7 57.0 53.0 62.4 43.5 68.5 33.6 54.6 51.8 59.8 42.3 65.7 32.5 52.2 50.5 57.1 41.1 62.7 31.5
10195
29 60.5 60.5 65.2 52.3 71.6 42.7 58.6 58.6 62.7 51.2 68.9 41.7 56.6 56.6 60.2 50.0 66.0 40.6 54.5 54.5 57.5 48.8 63.1 39.6
32 63.6 63.6 65.6 60.1 71.7 50.4 61.6 61.6 63.2 59.0 69.0 49.3 59.6 59.6 60.7 57.8 66.2 48.1 57.4 57.4 58.2 56.7 63.3 46.9
24 60.0 48.5 65.9 38.2 72.0 26.8 57.6 47.3 63.3 37.1 69.0 25.7 55.2 46.1 60.6 36.0 66.0 24.7 52.6 44.8 57.8 34.9 62.8 23.6
27 60.5 57.0 66.1 46.6 72.5 35.8 58.2 55.9 63.5 45.4 69.6 34.8 55.8 54.6 60.9 44.2 66.7 33.7 53.4 53.4 58.1 42.9 63.6 32.6
11340
29 62.5 62.5 66.5 55.0 72.8 44.6 60.5 60.5 63.9 53.8 70.0 43.6 58.4 58.4 61.2 52.6 66.8 42.1 56.2 56.2 58.5 51.4 63.9 40.9
32 65.7 65.7 67.0 63.6 73.0 52.8 63.6 63.6 64.6 62.4 70.2 51.7 61.5 61.5 62.0 61.3 67.3 50.5 59.2 59.2 59.3 59.3 64.3 49.3
24 61.0 50.5 66.9 39.5 72.9 27.2 58.5 49.3 64.2 38.4 69.8 26.2 56.0 48.0 61.4 37.3 66.7 25.1 53.4 46.7 58.3 35.7 63.4 24.0
27 61.7 59.8 67.1 48.4 73.5 36.9 59.3 58.6 64.5 47.2 70.5 35.9 56.8 56.8 61.8 46.0 67.5 34.8 54.5 54.5 58.9 44.7 64.4 33.7
12488
29 64.2 64.2 67.5 57.5 73.6 46.1 62.1 62.1 64.9 56.4 70.7 44.9 59.9 59.9 62.2 55.1 67.8 43.7 57.7 57.7 59.4 53.9 64.7 42.5
32 67.5 67.5 68.3 66.9 74.1 55.2 65.4 65.4 65.8 65.8 71.2 54.0 63.1 63.1 63.2 63.2 68.2 52.8 60.8 60.8 60.9 60.9 65.1 51.6
24 61.8 52.5 67.7 40.7 73.6 27.6 59.3 51.2 64.7 39.3 70.5 26.6 56.7 49.9 61.9 38.0 67.3 25.5 54.1 48.6 59.0 36.7 63.9 24.3
27 62.7 62.5 68.0 50.2 74.3 38.0 60.3 60.3 65.3 49.0 71.3 36.9 58.1 58.1 62.5 47.7 68.2 35.8 55.8 55.8 59.6 46.4 65.0 34.7
13633
29 65.8 65.8 68.4 60.0 74.5 47.7 63.6 63.6 65.8 58.8 71.6 46.5 61.3 61.3 63.0 57.6 68.5 45.3 59.0 59.0 60.2 56.3 65.4 44.0
32 69.2 69.2 69.2 69.2 74.9 57.5 66.9 66.9 67.0 67.0 72.0 56.3 64.6 64.6 64.7 64.7 69.0 55.1 62.2 62.2 62.2 62.2 65.8 53.8
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity