Performance
Data System
Table PD-9 Gross Cooling Capacities (MBh) TTA125B Condensing Unit with TWE100B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 108.2 79.4 117.8 61.3 124.3 42.2 100.3 76.1 109.3 58.1 115.4 39.2 92.3 72.8 100.8 54.9 106.5 36.1 84.4 69.5 92.3 51.7 97.6 33.0
80 108.2 93.1 117.8 75.0 124.3 55.9 100.3 89.8 109.3 71.8 115.4 52.8 92.3 86.5 100.8 68.5 106.5 49.7 84.4 82.7 92.3 65.3 97.6 46.7
3000
85 108.2 105.3 117.8 88.6 124.3 69.5 100.3 99.4 109.3 85.4 115.4 66.5 93.1 93.1 100.8 82.2 106.5 63.5 86.9 86.9 92.3 79.0 97.6 60.3
90 110.2 110.2 117.8 102.2 124.3 83.2 103.9 103.9 109.3 99.0 115.4 80.2 97.4 97.4 100.8 96.0 106.5 77.0 90.8 90.8 92.7 92.7 97.6 74.0
75 110.0 83.1 119.6 64.1 126.3 44.1 101.8 79.6 111.0 60.7 117.2 41.0 93.8 76.1 102.4 57.4 108.2 37.7 85.8 72.6 93.7 54.1 99.2 34.5
80 110.0 97.4 119.6 78.4 126.3 58.5 101.8 93.9 111.0 75.1 117.2 55.2 93.8 90.4 102.4 71.7 108.2 52.0 86.5 86.5 93.7 68.3 99.2 48.9
3325
85 110.1 110.1 119.6 92.7 126.3 72.7 104.0 104.0 111.0 89.3 117.2 69.6 97.4 97.4 102.4 85.9 108.2 66.4 90.9 90.9 93.7 82.7 99.2 63.1
90 115.3 115.3 119.6 106.9 126.3 87.0 108.7 108.7 111.0 103.6 117.2 83.9 101.9 101.9 102.4 100.4 108.2 80.6 95.0 95.0 96.9 96.9 99.2 77.4
75 111.8 87.0 121.7 67.1 128.4 46.2 103.6 83.3 112.9 63.6 119.2 43.0 95.4 79.7 104.1 60.2 110.1 39.5 87.2 76.1 95.3 56.6 100.8 36.1
80 111.8 102.0 121.7 82.1 128.4 61.3 103.6 98.3 112.9 78.6 119.2 57.9 95.4 94.7 104.1 75.1 110.1 54.5 90.6 90.6 95.3 71.6 100.8 51.2
3675
85 115.4 115.4 121.7 97.1 128.4 76.2 108.9 108.9 112.9 93.5 119.2 72.9 102.0 102.0 104.1 90.0 110.1 69.5 95.2 95.2 95.3 86.6 100.8 66.1
90 120.8 120.8 121.7 112.0 128.4 91.1 111.6 111.6 112.9 108.5 119.2 87.8 103.2 103.2 105.1 105.1 110.1 84.4 99.0 99.0 99.2 99.2 100.8 81.0
75 113.5 90.7 123.5 69.9 130.4 48.2 105.2 86.8 114.6 66.3 121.0 44.8 96.9 83.1 105.7 62.7 111.8 41.2 88.6 79.3 96.8 59.0 102.4 37.7
80 113.5 106.2 123.5 85.6 130.4 63.8 105.2 102.5 114.6 81.9 121.0 60.3 98.7 98.7 105.7 78.2 111.8 56.8 94.4 94.4 96.8 74.6 102.4 53.4
4000
85 120.2 120.2 123.5 101.2 130.4 79.4 113.5 113.5 114.6 97.5 121.0 75.9 104.8 104.8 105.7 93.8 111.8 72.4 96.1 96.1 96.8 90.2 102.4 68.9
90 123.1 123.1 123.5 116.7 130.4 94.9 113.5 113.5 114.6 113.0 121.0 91.5 107.6 107.6 109.5 109.5 111.8 87.9 99.8 99.8 101.5 101.5 102.4 84.4
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-9 Gross Cooling Capacities (kW) TTA125B Condensing Unit with TWE100B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9 31.7 23.3 34.5 18.0 36.4 12.4 29.4 22.3 32.0 17.0 33.8 11.5 27.0 21.3 29.5 16.1 31.2 10.6 24.7 20.4 27.0 15.1 28.6 9.7
26.7 31.7 27.3 34.5 22.0 36.4 16.4 29.4 26.3 32.0 21.0 33.8 15.5 27.0 25.3 29.5 20.1 31.2 14.6 24.7 24.2 27.0 19.1 28.6 13.7
5098
29.4 31.7 30.9 34.5 26.0 36.4 20.4 29.4 29.1 32.0 25.0 33.8 19.5 27.3 27.3 29.5 24.1 31.2 18.6 25.5 25.5 27.0 23.1 28.6 17.7
32.2 32.3 32.3 34.5 29.9 36.4 24.4 30.4 30.4 32.0 29.0 33.8 23.5 28.5 28.5 29.5 28.1 31.2 22.6 26.6 26.6 27.2 27.2 28.6 21.7
23.9 32.2 24.3 35.0 18.8 37.0 12.9 29.8 23.3 32.5 17.8 34.3 12.0 27.5 22.3 30.0 16.8 31.7 11.0 25.1 21.3 27.5 15.9 29.1 10.1
26.7 32.2 28.5 35.0 23.0 37.0 17.1 29.8 27.5 32.5 22.0 34.3 16.2 27.5 26.5 30.0 21.0 31.7 15.2 25.3 25.3 27.5 20.0 29.1 14.3
5648
29.4 32.3 32.3 35.0 27.2 37.0 21.3 30.5 30.5 32.5 26.2 34.3 20.4 28.5 28.5 30.0 25.2 31.7 19.5 26.6 26.6 27.5 24.2 29.1 18.5
32.2 33.8 33.8 35.0 31.3 37.0 25.5 31.8 31.8 32.5 30.4 34.3 24.6 29.9 29.9 30.0 29.4 31.7 23.6 27.8 27.8 28.4 28.4 29.1 22.7
23.9 32.8 25.5 35.7 19.7 37.6 13.5 30.4 24.4 33.1 18.6 34.9 12.6 28.0 23.4 30.5 17.6 32.3 11.6 25.5 22.3 27.9 16.6 29.5 10.6
26.7 32.8 29.9 35.7 24.1 37.6 18.0 30.4 28.8 33.1 23.0 34.9 17.0 28.0 27.7 30.5 22.0 32.3 16.0 26.5 26.5 27.9 21.0 29.5 15.0
6246
29.4 33.8 33.8 35.7 28.5 37.6 22.3 31.9 31.9 33.1 27.4 34.9 21.4 29.9 29.9 30.5 26.4 32.3 20.4 27.9 27.9 27.9 25.4 29.5 19.4
32.2 35.4 35.4 35.7 32.8 37.6 26.7 32.7 32.7 33.1 31.8 34.9 25.7 30.2 30.2 30.8 30.8
1
32.3 24.7 29.0 29.0 29.1 29.1 29.5 23.7
23.9 33.3 26.6 36.2 20.5 38.2 14.1 30.8 25.4 33.6 19.4 35.5 13.1 28.4 24.3 31.0 18.4 32.8 12.1 26.0 23.2 28.4 17.3 30.0 11.0
26.7 33.3 31.1 36.2 25.1 38.2 18.7 30.8 30.0 33.6 24.0 35.5 17.7 28.9 28.9 31.0 22.9 32.8 16.6 27.7 27.7 28.4 21.9 30.0 15.6
6797
29.4 35.2 35.2 36.2 29.7 38.2 23.3 33.3 33.3 33.6 28.6 35.5 22.2 30.7 30.7 31.0 27.5 32.8 21.2 28.2 28.2 28.4 26.4 30.0 20.2
32.2 36.1 36.1 36.2 34.2 38.2 27.8 33.3 33.3 33.6 33.1 35.5 26.8 31.5 31.5 32.1 32.1 32.8 25.8 29.2 29.2 29.7 29.7 30.0 24.7
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity