Data System
Table PD-8 Gross Cooling Capacities (MBh) - Single Compressor - TTA100C Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 62.7 60.3 68.8 49.8 75.3 29.4 60.1 59.0 65.9 48.6 72.1 28.4 57.3 57.3 62.8 47.4 68.7 27.3 54.8 54.8 59.7 46.1 65.2 26.2
80 65.8 65.8 69.1 57.4 75.9 41.9 63.5 63.5 66.2 56.2 72.6 40.5 61.0 61.0 63.2 54.9 69.4 39.3 58.5 58.5 60.2 53.6 66.0 37.9
3000
85 69.8 69.8 69.8 69.8 76.2 54.4 67.3 67.3 67.4 67.4 73.1 53.2 64.8 64.8 64.9 64.9 69.8 52.0 62.1 62.1 62.2 62.2 66.5 50.7
90 73.7 73.7 73.8 73.8 76.5 67.3 71.2 71.2 71.3 71.3 73.4 66.1 68.6 68.6 68.7 68.7 70.3 64.9 65.9 65.9 65.9 65.9 67.0 63.7
75 63.7 63.5 69.6 46.4 76.1 29.2 61.0 61.0 66.6 45.1 72.8 28.1 58.6 58.6 63.5 43.8 69.3 26.9 56.0 56.0 60.3 42.5 65.7 25.8
80 67.4 67.4 69.9 60.3 76.6 43.2 65.0 65.0 67.0 59.1 73.4 42.0 62.4 62.4 64.0 57.8 70.1 40.7 59.8 59.8 60.9 56.5 66.6 39.4
3325
85 71.5 71.5 71.5 71.5 77.0 57.0 69.0 69.0 69.0 69.0 73.8 55.8 66.3 66.3 66.4 66.4 70.5 54.6 63.5 63.5 63.6 63.6 67.1 53.4
90 75.6 75.6 75.6 75.6 77.5 71.1 73.0 73.0 73.0 73.0 74.4 69.9 70.3 70.3 70.3 70.3 71.2 68.7 67.4 67.4 67.5 67.5 67.9 67.5
75 64.8 64.8 70.3 55.6 76.7 31.0 62.3 62.3 67.3 54.3 73.3 30.0 59.8 59.8 64.1 45.6 69.8 28.9 57.1 57.1 60.9 44.2 66.1 27.8
80 68.9 68.9 70.7 63.3 77.3 44.7 66.3 66.3 67.8 62.1 74.1 43.5 63.7 63.7 64.7 60.8 70.7 42.2 61.0 61.0 61.6 59.5 67.2 40.8
3650
85 73.0 73.0 73.1 73.1 77.7 59.8 70.4 70.4 70.5 70.5 74.5 58.6 67.7 67.7 67.8 67.8 71.1 57.3 64.8 64.8 64.9 64.9 67.7 56.1
90 77.2 77.2 77.3 77.3 78.4 75.1 74.5 74.5 74.6 74.6 75.3 73.9 71.7 71.7 71.8 71.8 71.8 71.8 68.8 68.8 68.8 68.8 68.9 68.9
75 65.8 65.8 70.8 49.8 77.2 30.2 63.3 63.3 67.8 48.5 73.7 29.1 60.7 60.7 64.6 47.2 70.1 27.9 58.0 58.0 61.3 45.7 66.4 26.7
80 70.1 70.1 71.4 66.0 77.9 46.1 67.5 67.5 68.4 64.8 74.7 45.9 64.7 64.7 65.3 63.5 71.2 43.5 61.9 61.9 62.2 62.2 67.6 42.1
4000
85 74.3 74.3 74.4 74.4 78.3 62.2 71.6 71.6 71.7 71.7 75.0 61.0 68.8 68.8 68.9 68.9 71.6 59.8 65.9 65.9 66.0 66.0 68.2 58.5
90 78.6 78.6 78.7 78.7 79.2 78.7 75.8 75.8 75.9 75.9 75.9 75.9 72.9 72.9 73.0 73.0 73.1 73.1 69.9 69.9 70.0 70.0 70.0 70.0
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-8 Gross Cooling Capacities (kW) - Single Compressor - TTA100C Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 18.4 17.6 20.1 14.6 22.1 8.6 17.6 17.3 19.3 14.2 21.1 8.3 16.8 16.8 18.4 13.9 20.1 8.0 16.0 16.0 17.5 13.5 19.1 7.7
27 19.3 19.3 20.2 16.8 22.2 12.3 18.6 18.6 19.4 16.4 21.3 11.9 17.9 17.9 18.5 16.1 20.3 11.5 17.1 17.1 17.6 15.7 19.3 11.1
5098
29 20.4 20.4 20.4 20.4 22.3 15.9 19.7 19.7 19.7 19.7 21.4 15.6 19.0 19.0 19.0 19.0 20.4 15.2 18.2 18.2 18.2 18.2 19.5 14.9
32 21.6 21.6 21.6 21.6 22.4 19.7 20.9 20.9 20.9 20.9 21.5 19.4 20.1 20.1 20.1 20.1 20.6 19.0 19.3 19.3 19.3 19.3 19.6 18.7
24 18.7 18.6 20.4 13.6 22.3 8.5 17.9 17.9 19.5 13.2 21.3 8.2 17.2 17.2 18.6 12.8 20.3 7.9 16.4 16.4 17.7 12.4 19.2 7.5
27 19.7 19.7 20.5 17.7 22.4 12.6 19.0 19.0 19.6 17.3 21.5 12.3 18.3 18.3 18.7 16.9 20.5 11.9 17.5 17.5 17.8 16.5 19.5 11.5
5648
29 20.9 20.9 20.9 20.9 22.6 16.7 20.2 20.2 20.2 20.2 21.6 16.4 19.4 19.4 19.4 19.4 20.7 16.0 18.6 18.6 18.6 18.6 19.7 15.6
32 22.1 22.1 22.1 22.1 22.7 20.8 21.4 21.4 21.4 21.4 21.8 20.5 20.6 20.6 20.6 20.6 20.8 20.1 19.7 19.7 19.8 19.8 19.9 19.8
24 19.0 19.0 20.6 16.3 22.4 9.1 18.2 18.2 19.7 15.9 21.5 8.8 17.5 17.5 18.8 13.4 20.4 8.5 16.7 16.7 17.8 12.9 19.3 8.1
27 20.2 20.2 20.7 18.5 22.6 13.1 19.4 19.4 19.8 18.2 21.7 12.7 18.6 18.6 18.9 17.8 20.7 12.4 17.8 17.8 18.0 17.4 19.7 12.0
6203
29 21.4 21.4 21.4 21.4 22.8 17.5 20.6 20.6 20.6 20.6 21.8 17.1 19.8 19.8 19.8 19.8 20.8 16.8 19.0 19.0 19.0 19.0 19.8 16.4
32 22.6 22.6 22.6 22.6 23.0 22.0 21.8 21.8 21.8 21.8 22.0 21.6 21.0 21.0 21.0 21.0 21.0 21.0 20.1 20.1 20.2 20.2 20.2 20.2
24 19.3 19.3 20.7 14.6 22.6 8.8 18.5 18.5 19.9 14.2 21.6 8.5 17.8 17.8 18.9 13.8 20.5 8.2 17.0 17.0 18.0 13.4 19.4 7.8
27 20.5 20.5 20.9 19.3 22.8 13.5 19.8 19.8 20.0 19.0 21.9 13.4 19.0 19.0 19.1 18.6 20.8 12.7 18.1 18.1 18.2 18.2 19.8 12.3
6797
29 21.8 21.8 21.8 21.8 22.9 18.2 21.0 21.0 21.0 21.0 22.0 17.9 20.2 20.2 20.2 20.2 21.0 17.5 19.3 19.3 19.3 19.3 20.0 17.1
32 23.0 23.0 23.0 23.0 23.2 23.0 22.2 22.2 22.2 22.2 22.2 22.2 21.4 21.4 21.4 21.4 21.4 21.4 20.5 20.5 20.5 20.5 20.5 20.5
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity