Trane TWE050A-TWE200B Heat Pump User Manual


 
25SS-PRC003-EN
Performance
Data System
Table PD-13 Gross Cooling Capacities (MBh) - Both Compressors - TTA155C Condensing Unit With TWE155B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 147.1 118.2 163.0 98.8 180.4 66.6 141.7 115.6 156.9 96.3 173.3 64.1 135.4 112.5 149.9 93.6 165.4 61.4 128.3 109.1 142.1 90.5 156.9 58.5
80 147.9 138.6 163.3 113.9 180.5 87.8 142.7 136.0 157.2 111.3 173.4 85.1 136.7 133.1 150.1 108.1 165.5 82.2 130.0 129.8 142.3 104.8 157.1 79.1
4500
85 152.6 152.6 163.5 134.0 180.8 108.6 148.0 148.0 157.4 131.3 173.6 106.0 142.7 142.7 150.5 128.3 165.8 103.0 136.7 136.7 142.8 125.0 157.3 99.9
90 160.5 160.5 164.5 154.5 180.9 129.2 155.8 155.8 158.6 151.9 173.8 126.4 150.3 150.3 152.0 149.0 166.0 123.3 144.1 144.1 144.3 144.3 157.6 120.1
75 150.0 123.9 165.9 96.6 183.5 68.0 144.4 121.2 159.6 94.0 176.1 65.3 137.8 118.1 152.4 91.0 167.8 62.4 130.5 114.6 144.3 87.8 159.1 59.2
80 151.2 146.4 166.1 119.0 183.6 90.8 145.9 143.8 159.8 116.3 176.2 88.1 139.4 139.4 152.6 113.2 168.0 85.1 133.2 133.2 144.6 109.8 159.3 82.0
5000
85 157.6 157.6 166.5 141.1 183.8 113.6 152.8 152.8 160.2 138.4 176.5 110.9 147.2 147.2 153.1 135.3 168.3 107.9 140.9 140.9 145.2 132.0 159.7 104.8
90 165.9 165.9 168.1 163.7 184.0 135.8 160.9 160.9 162.1 161.1 176.7 133.0 155.1 155.1 155.2 155.2 168.6 129.9 148.6 148.6 148.7 148.7 159.9 126.6
75 152.4 129.4 168.4 100.0 185.9 69.1 146.6 126.6 161.8 97.3 178.3 66.3 139.9 123.4 154.4 94.3 169.9 63.3 132.5 120.0 146.2 91.0 161.0 60.2
80 154.3 153.9 168.6 124.0 186.1 93.7 148.6 148.6 162.0 121.2 178.5 91.0 143.0 143.0 154.7 118.1 170.0 87.9 136.6 136.6 146.5 114.7 161.2 84.8
5500
85 162.0 162.0 169.1 147.9 186.4 118.3 156.9 156.9 162.6 145.1 178.8 115.6 151.1 151.1 155.4 142.1 170.2 112.3 144.5 144.5 147.4 138.7 161.4 109.0
90 170.7 170.7 170.9 170.9 186.6 142.1 165.3 165.3 165.4 165.4 179.1 139.3 159.2 159.2 159.4 159.4 170.7 136.1 152.5 152.5 152.7 152.7 161.9 132.8
75 154.4 134.6 170.5 103.1 188.0 70.0 148.5 131.8 163.7 100.4 180.3 67.2 141.7 128.6 156.1 97.4 171.6 64.2 134.2 125.1 147.7 94.1 162.5 61.0
80 157.1 157.1 170.8 128.8 188.2 96.4 152.1 152.1 164.0 126.0 180.4 93.7 146.2 146.2 156.4 122.8 171.8 90.6 139.6 139.6 148.1 119.3 162.8 87.5
6000
85 165.9 165.9 171.5 154.6 188.6 122.9 160.6 160.6 164.8 151.7 180.6 119.8 154.5 154.5 157.5 148.6 172.1 116.6 147.7 147.7 149.5 145.3 163.1 113.2
90 174.9 174.9 175.1 175.1 188.9 148.3 169.2 169.2 169.4 169.4 181.1 145.4 162.8 162.8 163.0 163.0 172.6 142.2 155.9 155.9 156.1 156.1 163.5 138.9
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-13 Gross Cooling Capacities (kW) - Both Compressors - TTA155C Condensing Unit With TWE155B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 43.1 34.6 47.7 28.9 52.8 19.5 41.5 33.8 45.9 28.2 50.7 18.8 39.7 32.9 43.9 27.4 48.4 18.0 37.6 31.9 41.6 26.5 45.9 17.1
27 43.3 40.6 47.8 33.4 52.8 25.7 41.8 39.8 46.0 32.6 50.8 24.9 40.0 39.0 43.9 31.7 48.5 24.1 38.1 38.0 41.7 30.7 46.0 23.2
7646
29 44.7 44.7 47.9 39.2 52.9 31.8 43.3 43.3 46.1 38.5 50.8 31.0 41.8 41.8 44.1 37.6 48.5 30.2 40.0 40.0 41.8 36.6 46.1 29.3
32 47.0 47.0 48.2 45.2 53.0 37.8 45.6 45.6 46.4 44.5 50.9 37.0 44.0 44.0 44.5 43.6 48.6 36.1 42.2 42.2 42.3 42.3 46.1 35.2
24 43.9 36.3 48.6 28.3 53.7 19.9 42.3 35.5 46.7 27.5 51.6 19.1 40.4 34.6 44.6 26.7 49.1 18.3 38.2 33.6 42.3 25.7 46.6 17.3
27 44.3 42.9 48.6 34.9 53.7 26.6 42.7 42.1 46.8 34.1 51.6 25.8 40.8 40.8 44.7 33.2 49.2 24.9 39.0 39.0 42.3 32.2 46.7 24.0
8496
29 46.2 46.2 48.8 41.3 53.8 33.3 44.7 44.7 46.9 40.5 51.7 32.5 43.1 43.1 44.8 39.6 49.3 31.6 41.3 41.3 42.5 38.6 46.7 30.7
32 48.6 48.6 49.2 47.9 53.9 39.8 47.1 47.1 47.5 47.2 51.7 38.9 45.4 45.4 45.4 45.4 49.4 38.0 43.5 43.5 43.6 43.6 46.8 37.1
24 44.6 37.9 49.3 29.3 54.4 20.2 42.9 37.1 47.4 28.5 52.2 19.4 41.0 36.1 45.2 27.6 49.7 18.5 38.8 35.1 42.8 26.6 47.1 17.6
27 45.2 45.1 49.4 36.3 54.5 27.4 43.5 43.5 47.4 35.5 52.3 26.6 41.9 41.9 45.3 34.6 49.8 25.7 40.0 40.0 42.9 33.6 47.2 24.8
9346
29 47.4 47.4 49.5 43.3 54.6 34.6 46.0 46.0 47.6 42.5 52.4 33.8 44.2 44.2 45.5 41.6 49.8 32.9 42.3 42.3 43.2 40.6 47.3 31.9
32 50.0 50.0 50.0 50.0 54.6 41.6 48.4 48.4 48.4 48.4 52.4 40.8 46.6 46.6 46.7 46.7 50.0 39.9 44.6 44.6 44.7 44.7 47.4 38.9
24 45.2 39.4 49.9 30.2 55.1 20.5 43.5 38.6 47.9 29.4 52.8 19.7 41.5 37.7 45.7 28.5 50.2 18.8 39.3 36.6 43.3 27.5 47.6 17.9
27 46.0 46.0 50.0 37.7 55.1 28.2 44.5 44.5 48.0 36.9 52.8 27.4 42.8 42.8 45.8 36.0 50.3 26.5 40.9 40.9 43.4 34.9 47.7 25.6
10195 29 48.6 48.6 50.2 45.3 55.2 36.0 47.0 47.0 48.3 44.4 52.9 35.1 45.2 45.2 46.1 43.5 50.4 34.1 43.2 43.2 43.8 42.5 47.7 33.2
32 51.2 51.2 51.3 51.3 55.3 43.4 49.6 49.6 49.6 49.6 53.0 42.6 47.7 47.7 47.7 47.7 50.5 41.6 45.6 45.6 45.7 45.7 47.9 40.7
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity