14 SS-PRC003-EN
Performance
Data System
Table PD-2 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 79.9 65.5 87.9 54.1 95.9 35.7 76.9 64.0 84.5 52.7 92.0 34.4 73.5 62.2 80.7 51.2 87.7 32.9 69.6 60.3 76.4 49.5 82.9 31.3
80 80.7 77.2 88.1 62.8 96.6 48.0 77.9 75.8 84.8 61.3 92.8 46.6 74.6 74.1 81.0 59.6 88.6 45.1 70.8 70.8 76.8 57.7 84.0 43.5
2550 85 83.7 83.7 88.5 74.4 97.0 60.0 81.1 81.1 85.2 72.9 93.3 58.7 78.1 78.1 81.5 71.2 89.2 57.2 74.8 74.8 77.3 69.4 84.3 54.9
90 88.0 88.0 89.5 86.2 97.2 71.4 85.3 85.3 86.3 84.8 93.5 69.9 82.2 82.2 82.3 82.3 89.4 68.3 78.8 78.8 78.9 78.9 84.9 66.5
75 81.5 69.1 89.5 53.5 97.3 36.4 78.4 67.6 86.0 52.1 93.3 35.1 74.9 65.8 82.0 50.5 88.8 33.5 70.9 63.8 77.2 48.1 83.9 31.8
80 82.8 82.3 89.8 66.1 98.2 49.9 79.6 79.6 86.3 64.6 94.3 48.5 76.5 76.5 82.4 62.8 90.0 47.0 73.1 73.1 78.1 60.9 85.3 45.4
2875 85 86.7 86.7 90.3 79.0 98.6 63.3 83.9 83.9 86.9 77.5 94.5 61.3 80.8 80.8 83.1 75.8 90.3 59.6 77.2 77.2 78.9 73.9 85.7 57.8
90 91.2 91.2 91.2 91.2 98.8 75.6 88.3 88.3 88.4 88.4 95.1 74.1 85.1 85.1 85.2 85.2 90.8 72.5 81.4 81.4 81.5 81.5 86.2 70.7
75 82.9 72.6 90.8 55.7 98.5 37.0 79.8 71.0 86.9 53.7 94.3 35.6 76.1 69.2 82.8 51.9 89.7 34.1 72.1 67.2 78.3 49.9 84.6 32.4
80 84.6 84.6 91.2 69.3 99.4 51.8 81.8 81.8 87.6 67.7 95.5 50.4 78.6 78.6 83.6 65.9 91.1 48.9 75.0 75.0 79.1 63.9 86.3 47.2
3200 85 89.2 89.2 91.9 83.4 99.7 65.7 86.3 86.3 88.4 81.9 95.8 64.1 83.0 83.0 84.5 80.1 91.5 62.4 79.3 79.3 80.2 78.2 86.8 60.5
90 93.9 93.9 93.9 93.9 100.2 79.7 90.9 90.9 90.9 90.9 96.3 78.2 87.4 87.4 87.5 87.5 92.1 76.5 83.7 83.7 83.8 83.8 87.4 74.7
75 84.2 75.9 91.6 57.1 99.4 37.6 80.9 74.3 87.9 55.5 95.1 36.2 77.2 72.5 83.7 53.6 90.4 34.6 73.1 70.4 79.1 51.6 85.1 32.9
80 86.6 86.6 92.3 72.3 100.5 53.5 83.7 83.7 88.7 70.7 96.5 52.1 80.4 80.4 84.5 68.9 92.0 50.6 76.7 76.7 80.0 66.9 87.1 49.0
3525 85 91.4 91.4 93.2 87.7 100.9 68.4 88.4 88.4 89.7 86.1 96.9 66.8 84.9 84.9 85.8 84.4 92.5 65.1 81.1 81.1 81.2 81.2 87.7 63.1
90 96.2 96.2 96.2 96.2 101.4 83.6 93.0 93.0 93.1 93.1 97.5 82.1 89.5 89.5 89.6 89.6 93.1 80.4 85.6 85.6 85.7 85.7 88.5 78.6
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (kW) TTA075A Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9 23.4 19.2 25.7 15.8 28.1 10.5 22.5 18.7 24.7 15.4 26.9 10.1 21.5 18.2 23.6 15.0 25.7 9.6 20.4 17.7 22.4 14.5 24.3 9.2
26.7 23.6 22.6 25.8 18.4 28.3 14.0 22.8 22.2 24.8 18.0 27.2 13.6 21.8 21.7 23.7 17.5 26.0 13.2 20.7 20.7 22.5 16.9 24.6 12.7
4331
29.4 24.5 24.5 25.9 21.8 28.4 17.6 23.8 23.8 25.0 21.3 27.3 17.2 22.9 22.9 23.9 20.9 26.1 16.7 21.9 21.9 22.6 20.3 24.7 16.1
32.2 25.8 25.8 26.2 25.2 28.4 20.9 25.0 25.0 25.3 24.8 27.4 20.5 24.1 24.1 24.1 24.1 26.2 20.0 23.1 23.1 23.1 23.1 24.9 19.5
23.9 23.9 20.2 26.2 15.7 28.5 10.7 23.0 19.8 25.2 15.3 27.3 10.3 21.9 19.3 24.0 14.8 26.0 9.8 20.8 18.7 22.6 14.1 24.6 9.3
26.7 24.2 24.1 26.3 19.4 28.7 14.6 23.3 23.3 25.3 18.9 27.6 14.2 22.4 22.4 24.1 18.4 26.3 13.8 21.4 21.4 22.9 17.8 25.0 13.3
4885
29.4 25.4 25.4 26.4 23.1 28.9 18.5 24.6 24.6 25.5 22.7 27.7 18.0 23.7 23.7 24.3 22.2 26.4 17.5 22.6 22.6 23.1 21.6 25.1 16.9
32.2 26.7 26.7 26.7 26.7 28.9 22.1 25.9 25.9 25.9 25.9 27.8 21.7 24.9 24.9 24.9 24.9 26.6 21.2 23.8 23.8 23.9 23.9 25.3 20.7
23.9 24.3 21.2 26.6 16.3 28.8 10.8 23.4 20.8 25.4 15.7 27.6 10.4 22.3 20.3 24.2 15.2 26.3 10.0 21.1 19.7 22.9 14.6 24.8 9.5
26.7 24.8 24.8 26.7 20.3 29.1 15.2 24.0 24.0 25.7 19.8 28.0 14.8 23.0 23.0 24.5 19.3 26.7 14.3 22.0 22.0 23.2 18.7 25.3 13.8
5436
29.4 26.1 26.1 26.9 24.4 29.2 19.2 25.3 25.3 25.9 24.0 28.1 18.8 24.3 24.3 24.7 23.5 26.8 18.3 23.2 23.2 23.5 22.9 25.4 17.7
32.2 27.5 27.5 27.5 27.5 29.3 23.3 26.6 26.6 26.6 26.6 28.2 22.9 25.6 25.6 25.6 25.6 27.0 22.4 24.5 24.5 24.5 24.5 25.6 21.9
23.9 24.6 22.2 26.8 16.7 29.1 11.0 23.7 21.8 25.7 16.3 27.9 10.6 22.6 21.2 24.5 15.7 26.5 10.1 21.4 20.6 23.2 15.1 24.9 9.6
26.7 25.4 25.4 27.0 21.2 29.4 15.7 24.5 24.5 26.0 20.7 28.2 15.3 23.5 23.5 24.8 20.2 26.9 14.8 22.4 22.4 23.4 19.6 25.5 14.3
5990
29.4 26.8 26.8 27.3 25.7 29.5 20.0 25.9 25.9 26.3 25.2 28.4 19.6 24.9 24.9 25.1 24.7 27.1 19.0 23.7 23.7 23.8 23.8 25.7 18.5
32.2 28.2 28.2 28.2 28.2 29.7 24.5 27.2 27.2 27.3 27.3 28.5 24.0 26.2 26.2 26.2 26.2 27.3 23.5 25.1 25.1 25.1 25.1 25.9 23.0
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity