Trane TWE050A-TWE200B Heat Pump User Manual


 
13SS-PRC003-EN
Performance
Data System
Table PD-1 Gross Cooling Capacities (kW) TTA075A Condensing Unit with TWE075A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 22.2 17.5 24.5 14.7 26.9 9.9 21.4 17.0 23.6 14.3 25.8 9.6 20.5 16.6 22.5 13.9 24.6 9.2 19.4 16.0 21.4 13.4 23.3 8.7
27 22.3 20.4 24.5 16.8 26.9 13.1 21.5 20.0 23.6 16.4 25.9 12.7 20.6 19.5 22.6 15.9 24.8 12.3 19.6 19.0 21.4 15.4 23.5 11.8
3823
29 22.8 22.8 24.6 19.7 27.1 16.1 22.1 22.1 23.7 19.3 26.1 15.7 21.3 21.3 22.7 18.8 24.9 15.3 20.5 20.5 21.6 18.3 23.7 14.8
32 24.0 24.0 24.8 22.6 27.1 19.0 23.3 23.3 23.9 22.2 26.1 18.6 22.5 22.5 22.9 21.7 25.0 18.1 21.5 21.5 21.8 21.2 23.7 17.6
24 22.6 18.2 24.9 14.4 27.3 10.1 21.8 17.8 24.0 14.0 26.2 9.7 20.8 17.3 22.9 13.6 24.9 9.3 19.8 16.8 21.7 13.1 23.6 8.9
27 22.8 21.4 25.0 17.5 27.4 13.5 22.0 21.0 24.0 17.1 26.3 13.1 21.1 20.6 23.0 16.6 25.2 12.7 20.1 20.0 21.8 16.1 23.9 12.2
4248
29 23.5 23.5 25.1 20.7 27.5 16.8 22.8 22.8 24.2 20.3 26.5 16.4 22.0 22.0 23.1 19.8 25.2 15.9 21.1 21.1 21.9 19.3 24.0 15.3
32 24.8 24.8 25.3 23.9 27.6 19.9 24.0 24.0 24.4 23.5 26.5 19.5 23.2 23.2 23.4 23.0 25.4 19.0 22.2 22.2 22.2 22.2 24.1 18.5
24 23.0 19.0 25.3 14.9 27.6 10.3 22.2 18.6 24.3 14.5 26.5 9.9 21.2 18.1 23.2 14.0 25.2 9.5 20.0 17.5 21.9 13.4 23.8 9.0
27 23.2 22.5 25.4 18.2 27.8 13.9 22.4 22.1 24.4 17.8 26.7 13.5 21.4 21.4 23.3 17.3 25.5 13.1 20.5 20.5 22.1 16.8 24.2 12.6
4673
29 24.2 24.2 25.5 21.6 27.9 17.5 23.5 23.5 24.5 21.2 26.8 16.9 22.6 22.6 23.5 20.7 25.6 16.5 21.6 21.6 22.3 20.2 24.3 15.9
32 25.5 25.5 25.8 25.1 28.0 20.8 24.7 24.7 24.9 24.7 26.9 20.3 23.8 23.8 23.8 23.8 25.7 19.8 22.8 22.8 22.8 22.8 24.4 19.3
24 23.3 19.7 25.6 15.3 27.9 10.4 22.4 19.3 24.6 14.9 26.7 10.0 21.4 18.8 23.4 14.3 25.4 9.6 20.3 18.2 22.1 13.8 24.0 9.1
27 23.7 23.5 25.7 18.9 28.1 14.3 22.8 22.8 24.7 18.4 27.0 13.9 21.9 21.9 23.6 17.9 25.7 13.5 20.9 20.9 22.4 17.4 24.4 13.0
5098
29 24.8 24.8 25.8 22.5 28.1 18.0 24.0 24.0 24.9 22.1 27.1 17.5 23.1 23.1 23.8 21.6 25.8 17.0 22.1 22.1 22.6 21.1 24.5 16.5
32 26.1 26.1 26.1 26.1 28.3 21.6 25.3 25.3 25.3 25.3 27.2 21.2 24.3 24.3 24.4 24.4 26.0 20.7 23.3 23.3 23.3 23.3 24.7 20.2
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-1 Gross Cooling Capacities (MBh) TTA075A Condensing Unit with TWE075A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 75.7 59.6 83.5 50.1 91.7 34.0 73.1 58.2 80.5 48.8 88.2 32.7 69.9 56.6 76.9 47.4 84.1 31.3 66.3 54.8 72.9 45.8 79.5 29.8
80 76.2 69.5 83.7 57.4 92.0 44.6 73.6 68.1 80.6 56.0 88.6 43.3 70.5 66.6 77.1 54.4 84.7 41.8 67.0 64.8 73.2 52.6 80.3 40.3
2250
85 77.8 77.8 84.1 67.3 92.4 54.9 75.6 75.6 81.1 65.9 89.0 53.6 72.9 72.9 77.6 64.2 85.1 52.2 69.9 69.9 73.7 62.5 80.8 50.6
90 81.8 81.8 84.6 77.2 92.5 64.8 79.4 79.4 81.6 75.8 89.2 63.4 76.7 76.7 78.3 74.3 85.3 61.8 73.5 73.5 74.5 72.5 81.1 60.1
75 77.3 62.3 85.1 49.2 93.1 34.5 74.5 60.9 81.9 47.8 89.4 33.3 71.2 59.2 78.2 46.3 85.2 31.8 67.5 57.4 74.1 44.6 80.6 30.3
80 77.9 73.2 85.3 59.9 93.6 46.1 75.2 71.8 82.1 58.5 90.0 44.8 72.0 70.2 78.5 56.8 85.9 43.3 68.5 68.4 74.4 55.0 81.5 41.7
2500
85 80.4 80.4 85.7 70.6 94.0 57.4 78.0 78.0 82.6 69.2 90.4 56.0 75.2 75.2 78.9 67.6 86.2 54.1 72.0 72.0 74.9 65.7 81.8 52.4
90 84.6 84.6 86.4 81.6 94.2 67.9 82.0 82.0 83.4 80.2 90.7 66.5 79.1 79.1 79.9 78.6 86.7 64.9 75.8 75.8 75.9 75.9 82.4 63.1
75 78.6 64.9 86.3 50.8 94.2 35.2 75.7 63.4 83.0 49.4 90.4 33.9 72.3 61.7 79.3 47.9 86.1 32.4 68.5 59.8 74.7 45.7 81.4 30.8
80 79.4 76.7 86.6 62.2 94.8 47.5 76.6 75.3 83.3 60.8 91.1 46.2 73.1 73.1 79.6 59.1 87.0 44.7 69.9 69.9 75.5 57.2 82.5 43.1
2750
85 82.7 82.7 87.0 73.9 95.3 59.7 80.1 80.1 83.8 72.4 91.4 57.8 77.2 77.2 80.1 70.7 87.3 56.2 73.8 73.8 76.1 68.9 82.9 54.4
90 86.9 86.9 88.0 85.8 95.5 70.9 84.3 84.3 85.0 84.4 91.9 69.4 81.2 81.2 81.3 81.3 87.9 67.8 77.8 77.8 77.9 77.9 83.4 66.0
75 79.7 67.3 87.4 52.3 95.2 35.7 76.7 65.9 84.0 51.0 91.3 34.3 73.2 64.1 79.8 48.9 86.9 32.8 69.4 62.2 75.6 47.0 82.1 31.2
80 80.8 80.1 87.7 64.5 95.9 48.8 77.7 77.7 84.4 63.0 92.1 47.5 74.8 74.8 80.6 61.3 87.9 46.0 71.4 71.4 76.4 59.4 83.3 44.4
3000
85 84.6 84.6 88.2 77.0 96.1 61.3 82.0 82.0 84.9 75.5 92.4 59.8 78.9 78.9 81.2 73.8 88.3 58.2 75.5 75.5 77.1 72.0 83.8 56.3
90 89.0 89.0 89.1 89.1 96.7 73.7 86.3 86.3 86.4 86.4 93.0 72.3 83.1 83.1 83.2 83.2 88.8 70.6 79.6 79.6 79.6 79.6 84.3 68.8
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity