Toshiba RAM-SM560KRT-E Air Conditioner User Manual


 
12
Valve cover
Cord clamp
Piping cover
Indoor/outdoor
connecting cables
Power cable
6
ELECTRICAL WORK
Model RAV-
Power supply
Maximum running current
Installation fuse rating
Power cable
SM560AT-E SM800AT-E
220 240 V
Single phase 50 Hz
12A 15A
25 A (D type )
H07 RN-F or 245 IEC 66
(2.5 mm
2
or more)
For the air conditioner that has no power cable, connect
a power cable as mentioned below.
CAUTION
Wrong wiring may cause a burn-out to some
electrical parts.
Be sure to use the cord clamps attached to the
product.
Do not damage or scratch the conductive core
and inner insulator of power and inter-connecting
cables when peeling them.
Be sure to comply with local regulations of the
cable from outdoor unit to indoor unit.
(wire size and cabling method etc.)
Use the power and Inter-connecting cables with
specified thickness, specified type and protective
devices required.
<SM560AT-E>
How to remove the valve cover
1. Remove screws of the valve cover.
2. Pull the valve cover downward to remove it.
How to wire
1. Connect the connecting cable to the terminal as
identified with their respective numbers on the
terminal block of indoor and outdoor unit.
H07 RN-F or 245 IEC 66 (1.0 mm
2
or more)
2. When connecting the connecting cable to the
outdoor unit terminal, prevent water coming in the
outdoor unit.
3. Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
4. For inter connecting cable, do not use a wire jointed
to another on the way.
Use wires long enough to cover the entire length.
Power cable
Earth line Earth line
(mm)
10 10
10 10
LN
30 30
40 40
Connecting
cable
123
Stripping length power cord and connecting cable
CAUTION
The installation fuse (25A D type ) must
be used for the power supply line of this air
conditioner.
Incorrect/incomplete wiring might cause an
electrical fire or smoke.
Prepare the exclusive power supply for the air
conditioner.
This product can be connected to the mains.
Connection to the fixed wiring :
A switch which disconnects all poles and has a
contact separation of at least 3 mm must be
incorporated in the fixed wiring.
Terminal block
Screw
123LN
Connecting
cable
Power cable