Temco Tool DV1200N/P Indoor Fireplace User Manual


 
9
Temco DV1000/1200/1400 Series
76657
General Venting
When locating the vent termination, the minimum vent
clearances must be observed. (Page 10, Fig. 9)
NOTE: Local codes may require different clearances.
It is recommended that the termination not be located
within 24” (305mm) of garden sheds, fences, decks,
utility buildings or other obstructions.
Do not locate termination cap where excessive snow or
ice build up may occur. Be sure to check vent termina-
tion area after snow falls and clear to prevent accidental
blockage of venting system. When using snow blowers,
make sure snow is not directed towards vent termina-
tion area.
This appliance has a “special vent system”. Check
with local codes or in the absence of same, with CSA
B149.1 installation codes in Canada, or the current
National Fuel Gas Code ANSI Z223.1/NFPA 54 in the
USA, regarding special vent termination clearances.
These fireplaces are certified for use with four types of
venting systems
1. Temco 4” x 7” dia. flex vent.
2. Temco TDV series 4” x 7” dia. rigid vent.
3. Simpson Dura-Vent GS series 4” x 6⁵⁄₈” dia. vent.
4. Security Secure Vent series 4” x 6⁵⁄₈” dia. vent.
Review general venting information in this manual, and
information packed with the venting prior to starting the
installation of the fireplace.
Termination shall not be recessed into a wall or sid-
ing.
Horizontal sections must maintain a minimum 1/4”
rise per linear foot of horizontal run.
Combustible clearances from any horizontal vent
pipe area must be 2” (51 mm) from top of vent, and
1” (25 mm) from sides and bottom.
Clearance to combustibles from vertical pipe surface
is 1” (25 mm).