Quadra-Fire 21M-ACC Stove User Manual


 
May 5, 2011
7039-131H
Page17
2100 Millennium Wood Stove (ACC)
R
D. Chimney Termination Requirements
Followmanufacturer’sinstructionsforclearance,securing
ashingandterminatingthechimney.
Musthaveanapprovedandlistedcap
Mustnotbelocatedwhereitwillbecomepluggedby
snoworothermaterial
• Mustterminateatleast3feet(91cm)abovetheroof
andatleast2feet(61cm)aboveanyportionofthe
roofwithin10feet(305cm).
• Must be located away from trees or other struc-
tures
These are safety requirements and are not meant to assure proper ue draft.
Figure 17.1
E. 2-10-3 Rule
Figure 17.2
NOTE:
• Chimneyperformancemayvary.
• Trees,buildings,rooflinesandwindconditionsaffect
performance.
• Chimneyheightmayneedadjustmentifsmokingor
overdraftoccurs.
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)
3 ft. (91cm)
Minimum
10 ft. (305cm) To Nearest Roofline
2 ft. (61cm)
Pitched Roof
10 ft. (305cm) or more
3 ft. (91cm) Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Wall or Parapet
Flat Roof