Quadra-Fire 21M-ACC Stove User Manual


 
Page16
7039-131H
May 5, 2011
R
2100 Millennium Wood Stove (ACC)
Chimney Height / Rise and Run
Thisproductwasdesignedforandtestedona6inch(152mm)
chimney,14 to16 feet(420-480cm) high,(includes stove
height)measuredfromthebaseoftheappliance.Thefurther
yourstackheightordiametervariesfromthisconguration,
thepossibilityofperformanceproblemsexists.
Chimneyheightmayneedtobeincreased by2
-3%per
each1000feetabovesealevel.Itisnotrecommendedto
useoffsetsorelbowsataltitudesabove4000feetabovesea
levelorwhenthereareotherfactorsthataffectuedraft.
C. Installing Chimney Components
Chimney Connector
Singlewallconnectororstovepipe.
Thismustbeatleast24gaugemildsteelor26gaugeblue
steel.Thesectionsmustbeattachedtotheapplianceandto
eachotherwiththecrimped(male)endpointingtowardthe
stove.Alljoints,includingtheconnectionattheuecollar,
shouldbesecuredwith3sheetmetalscrews.Makesure
tofollowtheminimumclearancestocombustibles.Where
passagethroughthewall,orpartitionofcombustiblecon-
structionisdesiredinCanada,theinstallationshallconform
toCAN/CSA-B365.
Factory-builtlistedchimneyconnector(vented).
Alistedconnector(vented)mustbeusedwheninstallingthis
unitinamobilehome.Thelistedconnectorsmustconform
toeachothertoensureapropertandseal.
Flue Gas
Direction
Crimped
End
Toward
Stove
Secure pipe sections with a
minimum of 3 screws
Figure 16.2 Chimney Connector (Stove Pipe)
WARNING
• DONOTCONNECTTHISUNITTOACHIM-
NEYFLUESERVICINGANOTHERAPPLI-
ANCE.
• DONOTCONNECTTOANYAIRDISTRI-
BUTIONDUCTORSYSTEM.
Mayallowuegasestoenterthehouse.
Asphyxiation Risk.
Improperinstallation,adjustment,alteration,serviceor
maintenancecancauseinjuryorpropertydamage.Refer
totheowner’sinformationmanualprovidedwiththisappli-
ance.Forassistanceoradditionalinformationconsulta
qualiedinstaller,serviceagencyoryourdealer.
WARNING
Fire Risk.
InspectionofChimney:
• Chimneymustbeingoodcondition.
• MeetsminimumstandardofNFPA211
• Factory-builtchimneymustbe6inch
(152mm)UL103HT.
WARNING
WARNING
ONLYuseconnector:
• Withintheroom,betweenapplianceandceilingorwall.
ConnectorshallNOTpassthrough:
• Atticorroofspace
• Closetorsimilarconcealedspace
• Floororceiling
Maintainminimumclearancestocombustibles
Fire Risk.
FollowChimneyConnectorManufacturer’s
InstructionsforProperInstallation.
Chimney Flue
Liner
Fireclay
Liner or
Equivalent
Masonry Chimney
Constructed to NFPA 211
Wall Spacer
Wall Band
Trim Collar
Chimney
Connector
1 inch (25mm) Air
Space to Chimney
Section
Min. Clearance
2 inch (51mm)
Min. Chimney Clearance to
Wall Spacer and
Combustibles - 2 inch (51mm)
Chimney Section
Figure 16.1
Solid Pack Chimney with Metal Supports as a
Thimble (Cont’d)