Omega Vehicle Security OM5-C Electric Heater User Manual


 
16
OM5-ITC
Thermocouple Input Modules
The OM5-ITC modules are designed with a completely isolated computer
side circuit which can be floated to ±50V from Power Common, pin 16. This
complete isolation means that no connection is required between I/O
Common and Power Common for proper operation of the output switch. If
desired, the output switch can be turned on continuously by simply
connecting pin 22, the Read-Enable pin to I/O Common, pin 19.
The OM5-ITC can interface to nine industry standard thermocouple types:
J, K, T, E, R, S, C, N, and B. Its corresponding output signal operates over
a 0V to +5V range. Each module is cold-junction compensated to correct
for parasitic thermocouples formed by the thermocouple wire and screw
terminals on the mounting backpanel. Upscale open thermocouple detect
is provided by an internal pull-up resistor. Downscale indication can be
implemented by installing an external 47M resistor, ±20% tolerance,
between screw terminals 1 and 3 on the OM5-BP backpanels.
Signal filtering is accomplished with a six-pole filter which provides 95dB
of normal-mode-rejection at 60Hz and 90dB at 50Hz. Two poles of this filter
are on the field side of the isolation barrier, and the other four are on the
computer side.
After the initial field-side filtering, the input signal is chopped by a
proprietary chopper circuit. Isolation is provided by transformer coupling,
again using a proprietary technique to suppress transmission of common
mode spikes or surges. The module is powered from +5VDC, ±5%.
A special input circuit provides protection against accidental connection of
power-line voltages up to 240VAC.
FEATURES
INTERFACES TO TYPES J, K, T, E, R, S, C, N AND B
THERMOCOUPLES
HIGH LEVEL VOLTAGE OUTPUTS
1500Vrms TRANSFORMER ISOLATION
ANSI/IEEE C37.90.1-1989
TRANSIENT PROTECTION
INPUT PROTECTED TO 240VAC CONTINUOUS
160dB CMR
95dB NMR AT 60Hz, 90dB at 50Hz
±0.05% ACCURACY
±0.02% LINEARITY
±1µV/°C DRIFT
CSA CERTIFIED, FM APPROVED, CE COMPLIANT
MIX AND MATCH OM5 TYPES ON BACKPANEL
DESCRIPTION
Each OM5-ITC Thermocouple input module provides a single channel of
thermocouple input which is filtered, isolated, amplified, and converted to
a high level analog voltage output (Figure 1). This voltage output is logic-
switch controlled, allowing these modules to share a common analog bus
without the requirement of external multiplexers.
FIGURE 1. OM5-ITC Block Diagram.
–V
LPF
LPF
+In
–In
–EXC
Backpanel
Term Block
1
2
6
5
3
Surge
Suppression
and
Protection
+V
Isolated
Field-Side
Power
Power
Oscillator
Isolated
Computer-Side
Power
V
OUT
20
19
22
I/O Common
RD EN\
+5V
Power Common
4
3
2
1
+EXC
–V
+V
4
NC
Thermocouple
Precision
Reference
CJC
Temp
Sensor
+2.5V
17
16
100M
Isochopper™
Amplifier
Pat Pending