12
WI1370 XP-400 Installation Instructions
To eliminate this fixed 20-second entry
delay, also program zones as Exit/Entry
Follower Zones [02].
To return protection to zones of this type,
press
cb
from the keypad or
M
or
N
from a Keyfob. Program the Keyfob
AUX 1 or AUX 2 button for Full Set [81-7].
[02]Exit/Entry Follower Zones
Entry Delay allows the user time to enter
and disarm. Allows exit after the panel is
armed without setting off an immediate
alarm and allows entry only if an Exit/Entry
Zone [00] has been violated first. Zones of
this type have a three (3) minute power-up
delay, and do not display or cause an alarm
if faulted when the system powers up.
Pressing the
b
key cancels the 3 minute
timer.
Group Bypassing - Zones programmed as
Exit/Entry Follower Zones will be Group
bypassed if the
c
c
is pressed while
disarmed or within the Exit Delay.
Auto Interior Bypassing
- Also program zones
as Home/Away with Delay Zone(s) [01] to
automatically bypass at the expiration of the exit
delay if the EXIT/ENTRY Zone(s) are not
violated during the exit delay.
[03]Auto-Bypass Reentry Zones
Zones programmed as this zone type are
permitted to be faulted at the time of arming.
Once the zone is restored, while the control
panel is still armed, the zone will
automatically be unbypassed and any
subsequent violations of the zone will cause
an alarm condition.
[04]24-Hour Protection
A zone that provides protection at all times,
whether or not the system is armed.
[05]40 ms Loop Response
Normally loop response is 750 ms, select
this option to change the loop response to
40 ms. The slower the loop response, the
less sensitive the system will be to
intermittents (swingers). The programming
option is not permitted for UL installations.
[06]Open Circuit Zones
Program this zone type if unsupervised
normally open circuit devices are required
The programming option is not permitted for
UL installations.
[07]Burg (Steady) Output
Enables the Bell Output on a zone trip for
each zone selected. The Bell Output will
remain ON for the length of time
programmed for Burg (Steady) Output [07]
or it will remain ON until turned off by
entering a valid Arm/Disarm Code; 0 means
output will stay ON until reset.
If
A0
is
Entered during Exit Time, Home/
Away with Delay Zones will be automatically
bypassed, even if the Exit/Entry Zone is
violated. Easy Exit/Easy Arm [22-2] must be
enabled.
N
OTE
:
Normally Open Zone Wiring
Wire the normally
open contact
as shown (Zone 4).
EZ Zone Doubling
TM
resistor
is required.
Program the
zone for
Open Circuit [06].
(Z)
ZONE 1
(E)
2.2K
ZONE 4
FIGURE
5 O
PEN
C
IRCUIT
W
IRIING
3.9K