Mitsubishi Electronics PEFY-P-NMSU-E/PEFY-P-NMAU-E/PEFY-P-NMHU-E Indoor Furnishings User Manual


 
PEFY-9PEFY-P-NMSU-E/PEFY-P-NMAU-E/PEFY-P-NMHU-E (June 2010)
PEFY-P-NMSU-E
PEFY-P-NMAU-E
PEFY-P-NMHU-E
1. SPECIFICATIONS
Note: *1 Nominal cooling conditions *2 Nominal heating conditions Unit converter
Indoor:
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
kcal/h = kW x 860
BTU/h = kW x 3,412
Outdoor: 95degF D.B. (35degC D.B.)
47degF D.B. / 43degF W.B.
(8.3degC D.B. / 6.1degC W.B.)
cfm = m3/min x 35.31
lbs = kg / 0.4536
Pipe length: 25 ft. (7.6 m) 25 ft. (7.6 m)
*Above specication data is
subject to rounding variation.
Level difference: 0 ft. (0 m) 0 ft. (0 m)
*3 The rated external static pressure is set to 50 Pa (0.20 in. WG) for 208V and 150 Pa (0.60) for 230V at factory shipment.
*Due to continuing improvement, above specication may be subject to change without notice.
Model PEFY-P30NMHU-E PEFY-P36NMHU-E PEFY-P48NMHU-E PEFY-P54NMHU-E
Power source 1-phase 208/230 V 60Hz
Cooling capacityBTU / h 30,000 36,000 48,000 54,000
(Nominal)
W
8.8 10.6 14.1 15.8
Power input kW 0.326/0.3600.683/0.7540.683/0.75
40
.695/0.767
Current input A 1.66/1.83 3.38/3.73 3.38/3.73 3.43/3.78
Heating capacity *2 BTU / h
34,000 40,000 54,000 60,000
(Nominal)
kW
10.0 11.7 15.8 17.6
Power input kW
0.326/0.3600.683/0.7540.683/0.75
40
.695/0.767
Current input
A
1.66/1.83 3.38/3.73 3.38/3.73 3.43/3.78
External finish Galvanized
External dimension H x W x Din. 14-31/32 x 39-3/8 x 35-7/1614-31/32 x 47-1/4 x 35-7/1614-31/32 x 47-1/4 x 35-7/1614-31/32 x 47-1/4 x 35-7/16
mm 380 x 1,000 x 900 380 x 1,200 x 900 380 x 1,200 x 900380 x 1,200 x 900
Net weight lbs (kg) 111 (50) 155 (70) 155 (70) 155 (70)
Heat exchanger Cross fin(Aluminium fin and copper tube)
FAN Type x Quantity Sirocco fan x 1Sirocco fan x 2Sirocco fan x 2Sirocco fan x 2
*3
External
static
pressure
(208V) in.WG
Pa
(230V) in.WG
Pa
Motor type 1-phase induction motor
Motor output kW 0.2300.400 0.40
00
.400
Driving mechanism Direct-driven
Airflow rate cfm 636-883 936-1,342936-1,342 989-1,412
(Low-High) m3 / min18.0-25.0 26.5-38.0 26.5-38.
02
8.0-40.0
L / s 300-417 442-633 442-633 467-667
Sound pressure level (Low-High) dB <A>33-40 (208V)31-41 (208V) 31-41 (208V)31-41 (208V)
(measured in anechoic room) dB <A>38-43 (230V)38-44 (230V) 38-44 (230V) 38-44 (230V)
*3
dB <A>
----
Insulation material Polystyrene foam,Polyethylene foam,Urethane foam
Air filter Field-supplied; see Optional Parts
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A,R22 CITY MULTI
Diameter of Liquid(R410A)
in. (mm)
3/8 (9.52) Flare 3/8 (9.52) Flare 3/8 (9.52) Flare 3/8 (9.52) Flare
refrigerant pipe (R22 )3/8 (9.52) Flare3/8 (9.52) Flare3/8 (9.52) Flare3/8 (9.52) Flare
(O.D.) Gas(R410A)
in. (mm)
5/8 (15.88) Flare5/8 (15.88) Flare5/8 (15.88) Flare 5/8 (15.88) Flare
(R22 )5/8 (15.88) Flare3/4 (19.05) Flare3/4 (19.05) Flare 3/4 (19.05) Flare
Field drain pipe size in. (mm) O.D. 1-1/4 (32) O.D. 1-1/4 (32) O.D. 1-1/4 (32) O.D. 1-1/4 (32)
Drawing External W277664
Wiring W660134
Refrigerant cycle -
Standard Document Installation Manual,Installation Book
attachment Accessory Drain hose I.D. 1-1/4inch (32mm)(flexible joint)
Optional parts Drain pump PAC-KE04DM-F PAC-KE04DM-F PAC-KE04DM-F PAC-KE04DM-F
External heater adaptor
Filter box PAC-KE80TB-F PAC-KE140TB-F PAC-KE140TB-F PAC-KE140TB-F
Long life filter PAC-KE88LAF PAC-KE89LAF PAC-KE89LAF PAC-KE89LAF
Remarks *Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*Due to continuing improvement, above specification may be subject to change without notice.
CN24RELAY-KIT-CM3
CN24RELAY-KIT-CM3
CN24RELAY-KIT-CM3 CN24RELAY-KIT-CM3
(0.201*)-0.642 (208V)
(50*)-160
100-(150*)-200
0.401-(0.602*)-0.803 (230V)
(0.201*)-0.642 (208V)
(50*)-160
100-(150*)-200
0.401-(0.602*)-0.803 (230V)
(0.201*)-0.642 (208V)
(50*)-160
100-(150*)-200
0.401-(0.602*)-0.803 (230V)
(0.201*)-0.642 (208V)
(50*)-160
100-(150*)-200
0.401-(0.602*)-0.803 (230V)
k
*1
MCA 2.08 / 2.29 4.23 / 4.674.23 / 4.6
74
.29 / 4.73
A
Ventilation Air: Providing sufcient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.