External heater adaptor CN24RELAY-KIT-CM3 is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Item
External output cable
Connector
(for use with the panel heater)
Quantity 23
Shape
Refer to the Installation Manual for wiring and installation details.
For relay X use the specifications given below Operation coil
Rated voltage : 12VDC
Power consumption : 0.9W or less
The length of the electrical wiring for the CN24RELAY-KIT-CM3 is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm
2
~ 1.25 mm
2
(16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit
CN24
CN4Y
X
X
Remote control Board Relay circuit
Adapter
Indoor unit
control board
Outdoor unit
control board
Electric Heater
power source
Electric
Heater
Red 1
White
(for use with the panel heater)
2
Preparations in the field
Maximum cable length
is 10 m (32ft)
1
3
White
FS1
FS2
FS1
FS2
R
S
R
S
CN24
H2
88H
H1
88H
26H
88H
Wiring diagram
1-phase power
supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2----- Heater
26H--------- Overheat protection
thermostat
88H--------- Electromagnetic contactor
White
PUHY,PURY-P-TGMU
SW5-2 "ON"
PUHY,PURY-P-T/YHMU
SW5-10 "ON"
PUMY series
SW4-4 "ON"
PUHY,PURY-P-T/YJMU
SW5-10 "ON"
PUHY,PURY-HP-TJMU
SW5-10 "ON"
8-7. External Heater Adapter CN24RELAY-KIT-CM3 for PEFY-P-NMSU-E
8. OPTIONAL PARTS
If drain water can not flow out the Indoor unit by gravity and gradient, a Drain pump for draining is needed.
Drain pump PAC-KE04DM-F can pump water up to 550mm [21-21/32 in.] high from the drain pan.
Item Drain pump ass'y Separator Rubber plug Connector Dummy connector
Quantity 11211
Shape
Drain sensor
Drain socket
Item Rubber bushing Band PTT screw 4X10 Fixing plateInstallation manual
Quantity 126+1 (spare) 11
Shape
Detailed installation information should be referred to its Installation Manual (WT03312X02)