1. SPECIFICATIONS
Note: *1 Nominal cooling conditions *2 Nominal heating conditions Unit converter
Indoor:
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
kcal/h = kW x 860
BTU/h = kW x 3,412
Outdoor: 95degF D.B. (35degC D.B.)
47degF D.B. / 43degF W.B.
(8.3degC D.B. / 6.1degC W.B.)
cfm = m3/min x 35.31
lbs = kg / 0.4536
Pipe length: 25 ft. (7.6 m) 25 ft. (7.6 m)
*Above specication data is
subject to rounding variation.
Level difference: 0 ft. (0 m) 0 ft. (0 m)
*3 The rated external static pressure is set to 160 Pa (0.642 in. WG) for 208V and 200 Pa (0.803) for 230V at factory shipment.
*Due to continuing improvement, above specication may be subject to change without notice.
Model PEFY-P72NMHU-E PEFY-P96NMHU-E
Power source 3-phase 208/230 V 60Hz
Cooling capacity BTU / h 72,000 96,000
(Nominal)
kW
21.1 28.1
*3
Power inputkW 1.352/1.495 1.690/1.870
*3
Current inputA 4.48/4.945.69/6.28
Heating capacity
*2
BTU / h
80,000 108,000
(Nominal)
kW 23.4 31.7
Power inputkW
1.352/1.495 1.690/1.870
Current inputA
4.48/4.945.69/6.28
External finish Galvanized
External dimension H x W x Din. 18-17/32 x 49-7/32 x 44-1/8 18-17/32 x 49-7/32 x 44-1/8
mm 470 x 1,250 x 1,120 470 x 1,250 x 1,120
Net weightlbs (kg) 221 (100) 221 (100)
Heat exchanger Cross fin(Aluminium fin and copper tube)
FANType x Quantity Sirocco fan x 2Sirocco fan x 2
External-
static
pressure
(208V) in.WG
Pa
(230V) in.WG
Pa
Motor type 3-phase induction motor
Motor output kW 0.650 0.850
Driving mechanism Direct-driven
Airflow rate cfm2,048 2,541
m3 / min58.072.0
L / s967 1,200
Sound pressure leveldB <A>45 (208V)52 (208V)
(measured in anechoic room) dB <A>47 (230V) 54 (230V)
dB <A>- -
Insulation material Polystyrene foam,Polyethylene foam,Urethane foam
Air filter Field-supplied; see Optional Parts
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A,R22 CITY MULTI
Diameter of Liquid(R410A)
in. (mm)
3/8 (9.52) Brazed 3/8 (9.52) Brazed
refrigerant pipe (R22) 1/2 (12.7) Brazed 1/2 (12.7) Brazed
(O.D.) Gas (R410A)
in. (mm)
3/4 (19.05) Brazed 7/8 (22.2) Brazed
(R22 )1 (25.4) Brazed1-1/8 (28.58) Brazed
Field drain pipe size in. (mm) O.D. 1-1/4 (32) O.D. 1-1/4 (32)
DrawingExternal W277665
Wiring W660130
Refrigerant cycle -
Standard Document Installation Manual,Installation Book
attachment Accessory Drain hose I.D. 1-1/4inch (32mm)(flexible joint)
Optional partsDrain pump PAC-KE04DM-F PAC-KE04DM-F
External heater adaptor CN24RELAY-KIT-CM3
Filter box PAC-KE250TB-F PAC-KE250TB-F
Long life filter PAC-KE85LAF PAC-KE85LAF
Remarks *Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*Due to continuing improvement, above specification may be subject to change without notice.
*1
0.281-(0.642*) (208V)
70-(160*)
0.281-(0.642*) (208V)
70-(160*)
0.401-(0.803*) (230V)
100-(200*)
0.401-(0.803*) (230V)
100-(200*)
CN24RELAY-KIT-CM3
MCA 5.60 / 6.187.12 / 7.85
A
Ventilation Air: Providing sufcient ventilation air is an important part of every building design.