Mitsubishi Electronics PEFY-P-NMSU-E/PEFY-P-NMAU-E/PEFY-P-NMHU-E Indoor Furnishings User Manual


 
PEFY-3PEFY-P-NMSU-E/PEFY-P-NMAU-E/PEFY-P-NMHU-E (June 2010)
PEFY-P-NMSU-E
PEFY-P-NMAU-E
PEFY-P-NMHU-E
1. SPECIFICATIONS
Model PEFY-P06NMSU-E PEFY-P08NMSU-E PEFY-P12NMSU-E PEFY-P15NMSU-E
Power source 1-phase 208/230v 60Hz
Cooling capacity *1
(Nominal)
Btu / h 6,000 8,000 12,000 15,000
kW 1.8 2.3 3.5 4.4
Power input kW 0.05/0.05 0.06/0.06 0.07/0.07 0.07/0.07
Current input A 0.42/0.41 0.51/0.49 0.56/0.53 0.57/0.55
Heating capacity *2
(Nominal)
Btu / h 6,700 9,000 13,500 17,000
kW 2.0 2.6 4.0 5.0
Power input kW 0.03/0.03 0.04/0.04 0.05/0.05 0.05/0.05
Current input A 0.32/0.31 0.41/0.39 0.46/0.43 0.47/0.45
MCA A 0.47 / 0.50 0.47 / 0.50 0.68 / 0.74 1.20 / 1.33
External nish Galvanized
External dimension H x W x D
in. 7-7/8 X 31-1/8 X 27-9/16 7-7/8 X 31-1/8 X 27-9/16 7-7/8 X 31-1/8 X 27-9/16 7-7/8 X 39 X 27-9/16
mm 200 X 790 X 700 200 X 790 X 700 200 X 790 X 700 200 X 990 X 700
Net weight Lbs (kg) 42(19) 42(19) 46(20) 54(24)
Heat exchanger Cross n(aluminium n and copper tube)
Fan *4
Type x quantity Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2 SIROCCO FAN X 3
External
Static pressure
in.WG
0.02-(0.06*)-0.14-0.20
(208V)
0.02-(0.06*)-0.14-0.20
(208V)
0.02-(0.06*)-0.14-0.20
(208V)
0.02-(0.06*)-0.14-0.20
(208V)
PA 5-(15*)-35-50 5-(15*)-35-50 5-(15*)-35-50 5-(15*)-35-50
in.WG
0.02-(0.06*)-0.14-0.20
(230V)
0.02-(0.06*)-0.14-0.20
(230V)
0.02-(0.06*)-0.14-
0.20(230V)
0.02-(0.06*)-0.14-
0.20(230V)
PA 5-(15*)-35-50 5-(15*)-35-50 5-(15*)-35-50 5-(15*)-35-50
Motor type DC brushless motor
Motor output kW 0.096 0.096 0.096 0.096
Driving mechanism Direct-driven
Airow rate
(Low-Mid-High)
cfm
176-212-247 194-247-317 211-282-370 282-335-388
m
3
/ min. 5-6-7 5.5-7-9 6-8-10.5 8-9.5-11
L / s 83-100-117 91-116-150 100-133-175 133-158-183
Sound pressure level (Low-Mid-High)
(Measured in anechoic room) *4
dB <A> 22-24-28 (208V) 23-26-30 (208V) 23-28-35 (208V) 28-30-33 (208V)
dB<A> 22-24-28 (230V) 23-26-30 (230V) 23-28-35 (230V) 28-30-33 (230V)
dB <A> - - - -
Insulation material Polystyrene foam,polyethylene foam,urethane foam
Air lter PP honeycomb fabric (washable)
Protection Device Fuse
Refrigerant Control Device LEV
Connectable Outdoor Unit *3 R410A,R22 CITY MULTI R410A,R22 CITY MULTI R410A,R22 CITY MULTI
Diameter of
refrigerant pipe
(O.D.)
Liquid (R410A)
(R22 )
in. (mm)
1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed
1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed
Gas
(R410A)
(R22 )
in. (mm)
1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed
1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed
Diameter of drain pipe in. (mm) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32)
Drain lift mechanism in. (mm) 21-11/16 (551) 21-11/16 (551) 21-11/16 (551) 21-11/16 (551)
Drawing
External WKB94L522
Wiring WKB94L523
Refrigerant cycle -
Standard
Attachment
Document Installation manual, instruction book
Accessory Drain hose (exible joint)
Optional Parts External heater adaptor CN24RELAY-KIT-CM CN24RELAY-KIT-CM CN24RELAY-KIT-CM CN24RELAY-KIT-CM
Remark
Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
Note: *1 Nominal cooling conditions *2 Nominal heating conditions Unit converter
Indoor:
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
kcal/h = kW x 860
BTU/h = kW x 3,412
Outdoor: 95degF D.B. (35degC D.B.)
47degF D.B. / 43degF W.B.
(8.3degC D.B. / 6.1degC W.B.)
cfm = m3/min x 35.31
lbs = kg / 0.4536
Pipe length: 25 ft. (7.6 m) 25 ft. (7.6 m)
*Above specication data is
subject to rounding variation.
Level difference: 0 ft. (0 m) 0 ft. (0 m)
*3 PUHY-THMU,PURY-THMU,PUHY-YHMU,PURY-YHMU,PQHY, PQRY, PUHY-HP, PUMY-NHMU, PUHY-T/YHMU, PURY-T/YHMU
*4 The external static pressure is set to 15 Pa (0.06 in. WG) at factory shipment.
*Due to continuing improvement, above specication may be subject to change without notice.
Ventilation Air: Providing sufcient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local
codes.