Mitsubishi Electronics PEFY-P-NMSU-E/PEFY-P-NMAU-E/PEFY-P-NMHU-E Indoor Furnishings User Manual


 
PEFY-59PEFY-P-NMSU-E/PEFY-P-NMAU-E/PEFY-P-NMHU-E (June 2010)
PEFY-P-NMSU-E
PEFY-P-NMAU-E
PEFY-P-NMHU-E
Life span: 2,500 hr
*. The actual dust situation affects the filter life span, which should be considered at the applying site.
Material: Synthetic fiber unwoven cloth filter
For information regarding static pressure loss, see subsection 6. Fan Characteristic Curves.
Long-life filter should be used together with filter box PAC-KE-TB-F.
PAC-KE-LAF
ItemPAC-KE86LAF PAC-KE88LAF PAC-KE89LAF PAC-KE85LAF
Quantity 2332
Shape
(298X300) (298X300) (298X300) (411X600)
Detailed installation information should be referred to its Installation Manual (WT02574X04)
PAC-KE-TB-F
Item Screw Filter box Installation manual
Quantity 10/12* 11
Shape
*PAC-KE250TB has 12 pieces of screw..
Detailed installation information should be referred to its Installation Manual (WT03018X02, WT03019X02)
8-5. Long-life Filter PAC-KE-LAF; Filter Box PAC-KE-TB-F for PEFY-P-NMHU
8-6. External Heater Adapter CN24RELAY-KIT-CM3 for PEFY-P-NMHU/NMAU
8. OPTIONAL PARTS
External heater adaptor CN24RELAY-KIT-CM3 is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Item
External output cable
Fan speed setting cable
with resistance
Quantity 2
2
Shape
Refer to the Installation Manual for wiring and installation details.
For relay X use the specifications given below Operation coil
Rated voltage : 12VDC
Power consumption : 0.9W or less
The length of the electrical wiring for the CN24RELAY-KIT-CM3 is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm
2
~ 1.25 mm
2
(16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit
CN24
CN22
X
X
Remote control Board Relay circuit
Adapter
Indoor unit
control board
Outdoor unit
control board
Electric Heater
power source
Electric
Heater
Red 1
White 2
Preparations in the field
Maximum cable length
is 10 m (32ft)
1
2
WhiteGreen
FS1
FS2
FS1
FS2
R
S
R
S
CN24
H2
88H
H1
88H
26H
88H
Wiring diagram
1-phase power
supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2----- Heater
26H--------- Overheat protection
thermostat
88H--------- Electromagnetic contactor
White
PUHY,PURY-P-TGMU
SW5-2 "ON"
PUHY,PURY-P-T/YHMU
SW5-10 "ON"
PUMY series
SW4-4 "ON"
PUHY,PURY-P-T/YJMU
SW5-10 "ON"
PUHY,PURY-HP-TJMU