4-6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
MS24WN
Mode
FAN
COOL
565
487
Air flow
(CFM)
Air speed
(ft./sec.)
Coverage
range (ft.)
Function
Dry
Wet
34.2
29.4
20.1
17.2
4-7. ADDITIONAL REFRIGERANT CHARGE (R22(oz.))
MS24WN MU24WN
Outdoor unit
precharged
(up to 25ft.)
4 lb. 5 oz.
25ft.
0
30ft.
0.81
35ft.
1.62
Refrigerant piping length (one way)
40ft.
2.43
45ft.
3.24
50ft.
4.05
Model
CALCULATION : Xoz. = 0.81/ 5oz./ft. x (Additional Piping Length-25) ft.
(2) OPERATION
Function
Cooling
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
DB (˚F)
80
95
67
WB (˚F)
67
71
57
Indoor
78%
DB (˚F)
95
115
67
WB (˚F)
Outdoor
Condition
Intake air
temperature
The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizontally from
the unit properly at the High speed position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture
arranged in the room.
4-5. OPERATING RANGE
(1) POWER SUPPLY
Indoor unit
Outdoor unit
Rating
115V 60Hz 1[
208/230V 60Hz 1[
Guaranteed Voltage
MS24WN
MU24WN
Model
Min. 103V
Max. 127V
115V
Min. 198V Max. 253V
208V
230V