Majestic Appliances RDV4136 Indoor Fireplace User Manual


 
28
RDV4136 Series Direct Vent Gas Fireplace
10010618
Troubleshooting AF4000 Valve (continued)
Pilot will not light/stay lit
Verify the gas supply is turned on.
Verify the receiver is receiving the signal from the transmitter by listening for a
beep from the receiver when ON is pressed on the transmitter. If you do not hear
a beep, ensure the module has learned the transmitter (see above).
Ensure the orange lead from the pilot assembly igniter is securely connected to
the terminal labeled “I” and the white lead from the flame rectification sensor is
securely connected to the terminal labeled “S” on the control module. (Fig. 45)
Make sure the orange and white leads from the module are securely connected to
the terminals labeled “PILOT” on the valve body. (Fig. 48)
Ensure the black GROUND wire is securely connected to an appropriate metal
portion of the valve or pilot assembly. A proper ground is essential to spark
igniter operation.
Make certain the pilot flame is in contact with the flame rectification sensor on the
pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig.
48) If the pilot flame is too small it will not contact the flame rectification sensor
and will not complete the safety circuit.



6 Volt DC Adapter
Power Connection
8 Pin IPI
Connection
FP1764
Figure 47: AF4000 MOD Module End