Honeywell IFS-2600 Smoke Alarm User Manual


 
Page 70 IFS-2600 Installation & Programming Manual
P/N 10069 ECN08-0066
30W EVAC Slave Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg.
No.
Title
Sheet:
Drawn/
Traced
Engineer
Design
Approved
This Drawingmustnot be used for Construction
unless signed asapproved
7 Columbia Court,
Norwest Business Park
Baulkham Hills NSW 2153
AUSTRALIA
Tel
Fax
Email: support@inertia.com.au
A4
No.
Revision -reviseon CAD. Do notamend byhand Eng. App. Date
Copyright
This document is & shall
remain the propertyof
NotifierInertiaFireSystems
Unauthorised use ofthis
documentin anywayis
prohibited.
Drawing File No.
C
O
61 2 9894 1444
61 2 9899 4156
=DocumentFullPathAndName
Of:
+24
WARN
0V
REMOTE
REMOTE
OUTPUT
INPUT
+24V
0V
+24V
0V
EXTERNAL
POWER
MONITORJP1
AC INPUT
BATT
LINK JP1
+24
0V
AUX
+24V
0V
+24V COM
FAULT
ALERT OUT
EVAC OUT
ALARM
BGM EN
EVAC IN
ALERT IN
PTT
0V
PA+
PA -
BGM +
BGM -
VOLPA
+24
GND
COM
LINE +
30W EVAC
PCB 908
SHIELDED
BGMINPUT
1V P-P
FRONT
PANEL
EVAC
CONTROL
EOL
47K5%
SPEAKERSWITH
100V LINE TRANSFORMERS
ANDISOLATION CAPACITORS
SHIELDED
WHITE
RED
BLACK/SHIELD
BLUE
MICROPHONE
WITH PTT
4K7 5%
IFS-2600
30 WATTSLAVE
CONNECTION DIAGRAM
1 1
I PERRY25/8/05
I PERRY
2600-30W-SLAVE
A
TRANSFORMER
240V/20V
A
N
E
IFS1100
POWER SUPPLY
+24V
0V
AC1
AC2
IFS2600
TERMINATION
BOARD
JP2JP1
SOUND
BGMENABLE
( ENABLEDON
CLOSURE)
NOTE:
TOSLAVE TWOAMPLIFIERS
TOGETHER, REMOVETHEIFS903
BOARD FROMTHESLAVE
AMPLIFIER ANDCONNECT JP1
ON THEMASTERTO JP2ON THE
SLAVE.
THEMICROPHONEANDBGM
MUST ONLYBE CONNECTEDTO
THE MASTER AMPLIFIER.
CONNECT FAULTOUTPUTS
TOGETHER ANDMOVE THE
LASTWREON I/O PCBTO THE
FAULTTERMINALON THE
MASTER AMPLIFIER.
CONNECT PIN 4,P12 ON MASTER
TOPIN4 P12 ON SLAVE.
CONNECT TO
FAULT OUT
FROMSLAVE