Honeywell IFS-2600 Smoke Alarm User Manual


 
Page 66 IFS-2600 Installation & Programming Manual
P/N 10069 ECN08-0066
Smoke Spill Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg.
No.
Title
Sheet:
Drawn/
Traced
Engineer
Design
Approved
This Drawing must notbeused for Construction
unless signed asapproved
7 Columbia Court,
Norwest Business Park
Baulkham Hills NSW 2153
AUSTRALIA
Tel
Fax
Email: support@inertia.com.au
A4
No.
Revision -reviseon CAD. Do notamend byhand Eng. App. Date
Copyright
This document is&shall
remain the propertyof
NotifierInertia Fire Systems
Unauthoriseduse of this
documentin any wayis
prohibited.
Drawing File No.
C
O
61 2 9894 1444
61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24
0V
START1
STOP1
CONTROL
PCB1128
+24
START
STOP
RUN
STOP
FLT
INDICATION
FAN 1
COMMON+VE
FRONT PANEL CONTROL
FIREPANEL
FIELD WIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
SMOKE SPILL FAN (TYPICAL)
2600-SSF
FAN TERMINATION BOARD
AUX +24
AUX 0V
AUX POWER
CONTROL
FAN RUNNING
FAN STOPPEDAND POWER AVAILABLE
FAN FAULT ORNO POWER AVAILABLE
FAN START RELAY
RIBBON CABLE
1 1
(MAPPED TO ACF FOR
GENERAL ORZONED)
+24
0v
FIRE TRIP
ACF
PCB1125
-
+
IN
OUT
LOAD
-
+
-
+
D1
R1
FROM FIP
RELAY
* NOTE
EITHER THE MAPPING ABOVE MAY
BE USED TO START THE SSF
OR THE GENERAL ACF TRIP BELOW,
BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW
REQUIRES THAT THE MSSB
STARTS THE FAN.