Honeywell IFS-2600 Smoke Alarm User Manual


 
IFS-2600 Installation & Programming Manual Page 65
P/N 10069 ECN08-0066
Supply Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg.
No.
Title
Sheet:
Drawn/
Traced
Engineer
Design
Approved
This Drawing must not beusedforConstruction
unlesssigned asapproved
7 Columbia Court,
Norwest Business Park
Baulkham Hills NSW 2153
AUSTRALIA
Tel
Fax
Email: support@inertia.com.au
A4
No.
Revision -reviseon CAD. Donot amend byhand Eng. App. Date
Copyright
This document is &shall
remaintheproperty of
NotifierInertia FireSystems
Unauthoriseduse of this
documentin anywayis
prohibited.
DrawingFile No.
C
O
61 2 9894 1444
61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24
0V
START1
STOP1
CONTROL
PCB1128
+24
START
STOP
RUN
STOP
FLT
INDICATION
FAN 1
COMMON +VE
FRONT PANEL CONTROL
FIRE PANEL
FIELD WIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
SUPPLY AIR FAN (TYPICAL)
2600-SAF
FAN TERMINATION BOARD
AUX +24
AUX 0V
AUX POWER
CONTROL
FAN RUNNING
FAN STOPPED AND POWER AVAILABLE
FAN FAULT ORNO POWER AVAILABLE
FAN START RELAY
RIBBON CABLE
1 1
(MAPPED TOACF FOR
GENERAL OR ZONED)
+24
0v
FIRE TRIP
ACF
PCB1125
-
+
IN
OUT
LOAD
-
+
-
+
D1
R1
FROM FIP
RELAY
* NOTE
EITHER THE MAPPING ABOVE MAY
BE USED TO START THE SAF
OR THE GENERAL ACF TRIP BELOW,
BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW
REQUIRES THAT THE MSSB
STARTS THE FAN.
FAN STOP RELAY
(MAPPED TOAIR INTAKE
SMOKE DETECTOR)