IFS-2600 Installation & Programming Manual Page 63
P/N 10069 ECN08-0066
Dual Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg.
No.
Title
Sheet:
Drawn/
Traced
Engineer
Design
Approved
This Drawing must not beused for Construction
unless signed asapproved
7 Columbia Court,
Norwest Business Park
Baulkham Hills NSW 2153
AUSTRALIA
Tel
Fax
Email: support@inertia.com.au
A4
No.
Revision - reviseonCAD. Do notamendbyhand Eng. App. Date
Copyright
This document is&shall
remain the property of
NotifierInertia Fire Systems
Unauthoriseduseof this
document in anywayis
prohibited.
DrawingFile No.
C
O
61 2 9894 1444
61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24
0V
START1
START2
STOP1
STOP2
CONTROL
PCB1102
+24
START
+24
START
STOP
RUN
STOP
FLT
STOP
RUN
STOP
FLT
INDICATION
FAN 1
FAN 1
COMMON+VE
FAN 2
FAN 2
FRONT PANEL CONTROL
CONTROL
INDICATION
COMMON+VE
RUN
STOP
FAULT
FIRE PANEL
FIELDWIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD
MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE
PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
DUAL FAN (GENERAL)
2600-DUAL FAN
FAN TERMINATION BOARD
AUX +24
AUX 0V
AUX POWER
CONTROL
LINK SW1 A & B TO SW2 A, B
REMOVE SW2
FAN RUNNING
FAN STOPPED ANDPOWER AVAILABLE
FAN FAULT ORNO POWER AVAILABLE
FAN RUNNING
FAN STOPPED ANDPOWER AVAILABLE
FAN FAULT ORNO POWER AVAILABLE
OFF
AUTO
ON
FOR SINGLE CONTROL
*NOTE
FAN 1START RELAY
FAN 2START RELAY
FAN 1STOP RELAY
FAN 2STOP RELAY
RIBBON CABLE
1 1
START STOP