Honeywell HA40 Smoke Alarm User Manual


 
HA40 4-Channel Controller
Revision 1 (07/08)
HA40 Technical Manual 2-7
Unity Gain may be used at anytime to cancel incorrect calibrations
and start again. Unity means Offset = 0.00 and Gain = 1.00.
Figure 2-6. Cal Flow Chart
2�3 System Configuration Menus
Several items needing conguration are not specic to any channel
but affect the entire HA40 system. These are located in the SYSTEM
menus group shown in the dotted line box in Figure 2-7. System
menus are accessed through the SETUP menu shown in Figure 2-23
by pointing to the desired item and pressing Edit.
SETUP (firmware rev)
Channel 1
Channel 2
Channel 3
Channel 4
System
Security
History
Figure 2-7. System Conguration Menu
2�3�1 Standard / Optional Relay Setup Menus
The menu shown in Figure 2-8 allows conguring of both the standard
Relay 1 & Relay 2 motherboard relays and the six optional relays on
the 10-0222 discrete relay option PCB. Both standard and optional
relays are programmed in this menu. Select the relay to be congured
by pointing the arrow at the top menu item and pressing Edit. The
eld will scroll through all eight possible relays (2 standard and 6
optional).
Figure 2-8. Relay Setup Menu
Fault• , Alarm 1, Alarm 2, Alarm 3 menus (Figure 2-8) offer
additional “voting” exibility by controlling the channel alarm
combinations that will trip the selected relay. Each Votes entry
requires the specied quantity of that alarm to be active before
this relay activates. As illustrated in Figure 2-24 Standard Relay
1 activates when any 2 channels have Alarm 1 conditions,
PLUS, any one channel has an Alarm 2 condition. Fault Votes
and Alarm 3 Votes values are 0 therefore Fault and Alarm 3
conditions will not affect this relay.
Failsafe• set for YES causes this relay to be energized when
its voting requirements are false (no alarm condition) and de-
energized when the alarm vote requirements are true. The
primary benet of failsafe is loss of power places the relay
contacts into the alarm condition.