Heat Controller Water Source Heat Pump Water Heater User Manual


 
WattMaster WHP Section 4
4-22 Start-Up and Troubleshooting
5.1.2 General Troubleshooting Checklist
Begin troubleshooting by locating the general problem in the list below. Detailed
component troubleshooting information follows later in this section.
Zone is too warm
Is zone calling for cooling?
Is the compressor disabled due to minimum off time setting?
Is water proof of flow signal disabled?
Is the LED blinking an error code? See Figure 4-6.
Zone is too cool
Is zone calling for heating?
Is the compressor disabled due to minimum off time setting?
Is water proof of flow signal disabled?
Is the LED blinking an error code? See Figure 4-6.
Zone Sensor reading incorrectly
Is the sensor near a source of heat or a cold draft? Location is a common problem.
The sensor should be mounted on an inside wall away from heat sources and in a
location with adequate room air circulation.
Is the resistance reading correct? Check with the Temperature/Resistance Chart in
this section. (see page 4-42)
Is wiring correct? Check for errors.
Check the Room sensor
To meter the Room sensor:
Unplug the room sensor terminal block. Using your meter, check the resistance of the
unplugged terminal block. Use the supplied Temperature/Resistance Chart (page 4-
42) to see if the sensor is within a reasonable range. Readings which are much too
high or too low generally indicate wiring problems.
To meter the Slide Adjust (optional):
Use your ohmmeter to check the resistance between the room sensor GND wire and
the AIN2 terminal on the unplugged terminal block.
The resistance for various positions of the slider on the sensor should be as follows:
Full UP position
15K (± 500 )
MID position
12.5K (± 500 )
Full DN position
10K (± 500 )