Haier ESA412K Air Conditioner User Manual


 
no
yes
Alarm condition:outdoor DC motor is blocked rotor or broken, abnormal.
This fault is only used when indoor unit is with DC fan motor.
LCD of wall mounted unit display F2
4) Indoor DC motor abnormal
adjust fan blade to
make it run normally
adjust lead wire
of fan motor
yes
no
Check if the lead wire of DC motor
is broken or short-connected
Check if the indoor unit fan blade
is blocked by some objects
Replace motor
Warning: For outdoor DC fan motor, forbidden to pull off the plug when
being electrified.
Alarm condition: indoor coil temperature sensor value is abnormal;
or outdoor 4-way valve coil is invalid
Check if indoor coil
temp. sensor value is
normal
Replace coil
temp. sensor
LCD on wall mounted
unit displays E18
Check if resistor R34
on PCB is 20K
replace resistor
When only powering to outdoor
4-way valve coil, check if the coil
can reverse normally
replace 4-way valve
no
yes
no
yes
no
>a__WcU[S^ <[c >a`V[e[a`Wc
5) Temperature cutoff protection
-179-