Zone Programming
Important!: Note that before programming zone characteristics,
field 2*00 (number of partitions) and field 1*32 (receiver type)
must be programmed. This identifies the use of RF Receivers and
the number of partitions being used in the system.
Enter Programming mode, then press #93 to display "ZONE PROG?".
ZONE PROG?
1=YES 0=NO
Press 1 to enter ZONE PROGRAMMING mode. The
following screens will appear. Press [*] to display the
next screen. Press # to display a previous screen.
ENTER ZN NO.
00=QUIT 20
Enter the zone number to be programmed (01-64,
87-91, 92, 93, 95, 96, 97 or 99). Press [*] to accept
entry. Enter 00 to return to the main menu
selections.
Summary Screen -
Zn ZT P RC In:Ê L
20 00 1 00 RF:ÊN
A summary screen for that zone will appear. The "N"
after the colon indicates the loop number to which
the sensor is connected.
20 ZONE TYPE
ZONE DISABLED 00
Each zone in a system must be assigned to a zone
type, which defines the way in which the system
responds to faults in that zone. Refer to the ZONE
TYPE DEFINITIONS section for definitions of each
zone type. Enter the zone response type for each
zone. The screen will automatically display the zone
type for the number entered. Press [*] to accept
entry. If a different zone response type is desired,
enter a different number and press [*].
For UL applications, use of 1 or 2 RF receivers
requires enabling their respective faults (88-91) as
applicable (type 5).
Zone Types are as follows:
00 Assign for unused zones
01 Entry/Exit #1, burglary
02 Entry/exit #2,
03 Perimeter, burglary
04 Interior follower, burglary
05 Trouble by day/Alarm by night, burglary
06 24 hour silent alarm
07 24 hour audible alarm
08 24 hour auxiliary
09 Fire
10 Interior delay, burglary
20 Arm-stay (for 5800 transmitters only)
21 Arm-away (for 5800 transmitters only)
22 Disarm (for 5800 transmitters only)
23 No alarm response
20 PARTITION
Enter the partition number (1-2) in which this zone is
located.
20 REPORT CODE
Enter the report code for this zone.