Goodman Mfg SS-CPC36-72 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC36-72 www.goodmanmfg.com 9
heat kit eleCtriCal data (Blower only, heat mode) — 5 tons

 240 230 220 210 208
 1 0.93 0.82 0.78 0.76

 460 440 430
 0.92 0.84 0.8
For other voltage use voltage² / 480²

 560 550 540
 0.95 0.91 0.88
Mulply rated kW by correcon factor to get actual kW











CPC060***1D*** 42 60
EHK1-10 53 / 62 60 / 70 10 1750-2250 CFM T3, T4, T5
EHK1-15 76 / 88 80 / 90 15 1750-2250 CFM T3, T4, T5
EHK1-20 99 / 114 100 / 120 20 1850-2250 CFM T5
CPC060***3D*** 29 45
EHK3-10 34 / 40 35 / 45 10 1750-2250 CFM T3, T4, T5
EHK3-15 47 / 55 50 / 60 15 1750-2250 CFM T3, T4, T5
EHK3-20 60 / 70 70 / 70 20 1850-2250 CFM T5
CPC060***3B*** 25 40 ---
EHK3-10 30 / 35 35 / 40 10 1750 - 2250 CFM ---
EHK3-15 43 / 50 45 / 50 15 1750 - 2250 CFM ---
EHK3-20 56 / 65 60 / 70 20 1850 - 2250 CFM ---










CPC060***4B*** 12 20
EHK4-10 19 20 10 1750 - 2250 CFM
EHK4-15 25 25 15 1750 - 2250 CFM
EHK4-20 35 35 20 1850 - 2250 CFM










CPC060***7B*** 10 15
EHK7-10 15 20 10 1750-2250 CFM
EHK7-15 22 25 15 1750-2250 CFM
EHK7-20 28 30 20 1850-2250 CFM
EHK7-25 34 35 25 ---
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon Device
kw CorreCtion faCtor



 
10 1,750 1,700
15 1,750 1,700
20 1,850 1,880