Goodman Mfg SS-CPC36-72 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC36-72 www.goodmanmfg.com 7
heat kit eleCtriCal data (Blower only, heat mode) — 3 tons

 240 230 220 210 208
 1 0.93 0.82 0.78 0.76
Mulply rated kW by correcon factor to get actual kW

 460 440 430
 0.92 0.84 0.8
For other voltage use voltage
2
/ 480
2

 560 550 540
 0.95 0.91 0.88
Mulply rated kW by correcon factor to get actual kW
kw CorreCtion faCtor










CPC036***1D*** 25 40
EHK1-10 48 / 55 50 / 60 10 1250-1350 CFM
EHK1-15 70 / 81 80 / 90 15 1400-1440 CFM
CPC036***3D*** 17 25
EHK3-10 29 / 33 30 / 35 10 1250-1350 CFM
EHK3-15 42 / 48 45 / 50 15 1400-1440 CFM
CPC036***3B*** 18 25
EHK3-10 30 / 33 35 / 35 10 1250-1350 CFM
EHK3-15 43 / 48 45 / 50 15 1400-1440 CFM










CPC036***4B*** 10 15
EHK4-10 17 20 10 1250-1350 CFM
EHK4-15 25 25 15 1400-1440 CFM










CPC036***7B*** 8 15
EHK7-10 15 20 10 1250-1350 CFM
EHK7-15 22 25 15 1400-1440 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device



 
10 kW 1,250 1,250
15 kW 1,400 1,250