Goodman Mfg SS-CPC36-72 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
10 www.goodmanmfg.com SS-CPC36-72
heat kit eleCtriCal data (Blower only, heat mode) — 6 tons

Supply Voltage 240 230 220 210
Correcon Factor 1 0.92 0.84 0.77

Actual Voltage 460 440 430
Correcon Factor 0.92 0.84 0.8
For other voltage use voltage² / 480²

Supply Voltage 560 550 540
Correcon Factor 0.95 0.91 0.88
Mulply rated kW by correcon factor to get actual kW.

 
10 2,100
15 2,100
20 2,100
25 2,100










CPC072XXX3BXXX 31 45
EHK3-10 36 45 10 2,100 - 2,700 CFM
EHK3-15 51 60 15 2,100 - 2,700 CFM
EHK3-20 66 70 20 2,100 - 2,700 CFM
EHK3-25 81 90 25 2,100 - 2,700 CFM










CPC072XXX4BXXX 16 25
EHK4-10 18 25 10 2,100 - 2,700 CFM
EHK4-15 26 30 15 2,100 - 2,700 CFM
EHK4-20 33 35 20 2,100 - 2,700 CFM
EHK4-25 41 45 25 2,100 - 2,700 CFM










CPC072XXX7BXXX 13 15
EHK7-10 15 20 10 2,100 - 2,700 CFM
EHK7-15 22 25 15 2,100 - 2,700 CFM
EHK7-20 28 30 20 2,100 - 2,700 CFM
EHK7-25 34 35 25 2,100 - 2,700 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon Device
Note: All heaters have single-point entry kit