prodUCt speCifiCations
prodUCt speCifiCations
10 www.goodmanmfg.com SS-CPC36-72
heat kit eleCtriCal data (Blower only, heat mode) — 6 tons
Supply Voltage 240 230 220 210
Correcon Factor 1 0.92 0.84 0.77
Actual Voltage 460 440 430
Correcon Factor 0.92 0.84 0.8
For other voltage use voltage² / 480²
Supply Voltage 560 550 540
Correcon Factor 0.95 0.91 0.88
Mulply rated kW by correcon factor to get actual kW.
10 2,100
15 2,100
20 2,100
25 2,100
CPC072XXX3BXXX 31 45
EHK3-10 36 45 10 2,100 - 2,700 CFM
EHK3-15 51 60 15 2,100 - 2,700 CFM
EHK3-20 66 70 20 2,100 - 2,700 CFM
EHK3-25 81 90 25 2,100 - 2,700 CFM
CPC072XXX4BXXX 16 25
EHK4-10 18 25 10 2,100 - 2,700 CFM
EHK4-15 26 30 15 2,100 - 2,700 CFM
EHK4-20 33 35 20 2,100 - 2,700 CFM
EHK4-25 41 45 25 2,100 - 2,700 CFM
CPC072XXX7BXXX 13 15
EHK7-10 15 20 10 2,100 - 2,700 CFM
EHK7-15 22 25 15 2,100 - 2,700 CFM
EHK7-20 28 30 20 2,100 - 2,700 CFM
EHK7-25 34 35 25 2,100 - 2,700 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon Device
Note: All heaters have single-point entry kit