Goodman Mfg SS-CPC36-72 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
12 www.goodmanmfg.com SS-CPC36-72
airflow data — CpC036 (Cont.)
standard Belt drive — horizontal



     
           
0.2 1658 0.35 1489 0.28
0.4 1560 0.36 1339 0.28 1129 0.21
0.6 1682 0.47 1436 0.36 1196 0.27 949 0.19
0.8 1581 0.50 1354 0.38 1096 0.28 828 0.18
1.0 1266 0.39 994 0.28 756 0.19
1.2 923 0.28
high-statiC Belt drive — horizontal



     
           
0.6 1742 0.50 1431 0.36
0.8 1626 0.52 1357 0.39 1078 0.27
1.0 1611 0.56 1315 0.42 1011 0.28
1.2 1605 0.62 1299 0.46 976 0.31
1.4 1605 0.68 1281 0.51 959 0.35
1.6 1281 0.57 981 0.41
1.8 981 0.47
standard Belt drive — down shot



     
           
0.2 1424 0.30 1239 0.23
0.4 1520 0.39 1292 0.29 1073 0.22 779 0.14
0.6 1439 0.40 1192 0.30 944 0.21 619 0.12
0.8 1350 0.42 1101 0.31 864 0.22
1.0 1028 0.31 729 0.21
1.2 675 0.20
high-statiC Belt drive — down shot



     
           
0.6 1692 0.54 1449 0.41 1173 0.29
0.8 1678 0.58 1397 0.44 1107 0.31 854 0.21
1.0 1681 0.65 1381 0.49 1078 0.34 794 0.22
1.2 1681 0.71 1362 0.54 1062 0.39
1.4 1362 0.60 1066 0.44
1.6 1066 0.50 789 0.34
1.8 789 0.40