Goodman Mfg SS-CPC36-72 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
28 www.goodmanmfg.com SS-CPC36-72
roof CUrB installation — rigging
Provisionsforforkshavebeenincludedintheunitbaseframe.Nootherfork
locationsareapproved.
• Unitmustbeliftedbythefourliftingholeslocatedatthebaseframe
corners.
• Liftingcablesshouldbeattachedtotheunitwithshackles.
• Thedistancebetweenthecranehookandthetopoftheunitmustnot
belessthan60”.
• Twospreaderbarsmustspanovertheunittopreventdamagetothe
cabinet by the lift cables.Spreader bars mustbe of sufcient length
sothatcablesdonotcomeincontactwiththeunitduringtransport.
Remove wood struts mounted beneath unit base frame before set-
tingunitonroofcurb.Thesestrutsareintendedtoprotectunitbase
frame from forklift damage. To remove thestruts, extract the sheet
metal retainers and pull the struts through the base of the unit.
Refertorigginglabelontheunit.
Important:Ifusingbottomdischargewithroofcurb,duct-workshouldbe
attachedtothecurbpriortoinstallingtheunit.Duct-workdimensionsare
showninRoofCurbInstallationInstructionsManual.
RefertotheRoofCurbInstallationInstructionsforpropercurbinstallation.
CurbingmustbeinstalledincompliancewiththeNationalRoongContractorsAssociationManual.
Lowerunitcarefullyontoroofmountingcurb.Whileriggingtheunit,thecenterofgravitywillcausethecondenserendtobelower
thanthesupplyairend.
Bringcondenserendofunitintoalignmentwiththecurb.Withcondenserendoftheunitrestingoncurbmemberandusingcurbas
afulcrum,loweroppositeendoftheunituntilentireunitisseatedonthecurb.Whenarectangularcantilevercurbisused,takecare
tocentertheunit.Checkforproperalignmentandorientationofsupplyandreturnopeningswithduct.
Toassistindeterminingriggingrequirements,unitweightsareshownbelow.
Corner & Center-of-gravity loCations
30”
Compressor
Return
Evaporator Coil
Supply
Condenser
Coil
37”









Corner Weight (A) 115 120 130
150
Corner Weight (B) 150 150 160
190
Corner Weight (C) 105 105 115
130
Corner Weight (D) 130 135 150
170
Unit Shipping Weight 525 540 580
665
Unit Operang Weight 500 515 555
640
Note: Weights are calculated without accessories installed.