GE 6100 Air Conditioner User Manual


 
56
General Installation Suggestions
Ducted Installation Comments
New Installations
The GE Zoneline
®
4100 and 6100 Series are approved for
ducted installation using the GE Duct Adapter model RAK6052
and the GE Duct Extension RAK601. A field-fabricated duct
extension with the same interior measurements as the RAK601
may be used with the RAK6052 duct adapter. GE does not
recommend ducting in more than one direction.
The use of a duct adapter other than the RAK6052 is not
approved by GE and may cause problems such as inadequate
airflow to the secondary room or the unit shutting off on one
of the overload devices.
Failure to allow for adequate air return from the secondary
room is often the cause of less than satisfactory performance
of a ducted installation.
Replacement Installations
GE offers duct adapters to allow for easy replacements of
previous-design chassis in ducted installations where a GE
duct adapter was used in the original installation. A duct
adapter is available that will align with the duct extension
when GE-built components were used in the original installation.
The duct adaptor/extension used from the early 1960s until
late 1987 was 8-3/8" high by 6-1/2" wide. If the chassis to be
replaced is the flat-top discharge (design until late 1987) the
duct adapter model RAK7012 will align with the existing duct
extension. This means the duct extension will not have to be
changed. However, to keep the cost of the replacement to a
minimum there are components that will need to be taken
off the existing installation and used on the RAK7012 duct
adapter. The wall case mounting brackets, screws, discharge
grille, damper and end cap will need to be retained.
If the chassis is a slope-front discharge and the duct
dimensions are 8-3/8" high by 6-1/2" wide, then the
chassis has already been replaced and the purchase
of a new duct adapter is not required. The only piece that
needs to be replaced in this installation is the transition
piece, model RAK7022, which fits between the chassis and
the duct adapter.
If the chassis being replaced has a model number that
begins with AZ22, AZ25, AZ28, AZ29, AZ32, AZ35, AZ38 or
AZ39, the new 4100 or 6100 Series unit can be installed using
the same duct components.
If the existing chassis is a slope-front discharge and the duct
dimensions are 7-3/32" high by 6-1/2" wide, only the RAK7022
transition piece is required to install a 4100 or 6100 Series
unit in the ducted installation.
There were a number of Zoneline units installed in ducted
installations that did not use a GE duct adapter. The easiest
way to determine if the existing duct adapter is a GE duct
adapter is to compare the duct adapter dimensions to the
dimensions above. If the dimensions are different from the
dimensions above or it the duct adapter is not made of sheet
metal, it is not a GE duct adapter. In such installations GE
recommends the removal of the old duct adapter and duct
extension and the installation of a RAK6052 duct adapter
and a RAK601 duct extension. Zoneline units installed in
installations not using GE duct adapters and an extension
with the same cross-section dimensions as the duct adapter
may not be covered by the warranty.
What is covered
Limited one-year warranty
For one year from the date of the original purchase, GE will repair or
replace any part of the air conditioner which fails due to a defect in
materials or workmanship. During this limited one-year warranty, GE
will provide, free of charge, all labor and related service costs to repair
or replace the defective part.
Limited five-year warranty
For five years from the date of the original purchase, GE will repair
or replace the Sealed Refrigerating System if any part of the Sealed
Refrigerating System (the compressor, condenser, evaporator, and
all connecting tubing) should fail due to a defect in materials or
workmanship. During this limited five-year warranty, GE will provide,
free of charge, all labor and related service costs to repair or replace
the defective part.
Limited second-through-fifth-year parts warranty
From the second through the fifth year from the date of the original
purchase, GE will replace the Fan Motors, Switches, Thermostat, Heater,
Heater Protectors, Compressor Overload, Solenoids, Circuit Boards,
Auxiliary Controls, Thermistors, Freeze Sentinel
, Frost Controls, ICR
Pump, Capacitors, Varistors and Indoor Blower Bearing, if any of these
parts should fail due to a defect in materials or workmanship. During this
additional four-year limited warranty, you will be responsible for any
labor and related service costs.
*See written warranty for details
Zoneline Warranty*