GE 6100 Air Conditioner User Manual


 
20
OVER 40 FT.
CORRECT
High Wall Mount — For units
mounted high in the wall, the
discharge louvers should be
at a setting that provides the
most horizontal air discharge.
Recommended installation is
at least 3" below the ceiling. In
installations where units are close to the ceiling, the greatest
horizontal discharge angle can be obtained by removing
the discharge grille from the room cabinet.
Supply Air Throw — One Zoneline unit should not be required
to do a job obviously requiring two or more units. Units
should be located around large rooms according to
calculated loads or in such fashion as to achieve balanced
air distribution in all parts of the room. The single unit in
the “Incorrect” illustration below obviously cannot condition
the entire room. Add a second unit as shown in the
“Correct” illustration.
Application Comments
Use and Care Manual and installation instructions are
shipped with Zoneline
®
units. It is important that any air
conditioning system be properly sized and applied in order
to achieve the desired temperature and humidity levels in
the space to be conditioned. Zoneline units are designed
primarily to provide heating and cooling with the additional
benefit that during operation in the cooling mode, the units
also remove some moisture from the conditioned space.
The following are some brief application comments on
undersizing, oversizing, heating, wall coverings, and air
infiltration: all are important in the proper matching of the
heating/air conditioning system to the building structure.
Undersizing: If an air conditioner is undersized (cooling
capacity is less than required for a specific application), the
unit will typically not be able to cool the space down to the
desired temperature (thermostat set point), nor be able to
remove enough moisture from the air. A result could be a
warm and humid or warm and dry conditioned space.
Oversizing: If an air conditioner is oversized (cooling capacity
is greater than required for the specific application), the unit
will typically cool the space down to the desired temperature
(thermostat set point) too quickly. The compressor then
begins to cycle on and off. Dehumidification only takes place
when the compressor is operating. A typical result in a hot/
humid climate could be a cool but excessively humid space.
Heating: Undersizing can result in not being able to maintain
the desired temperature level within the conditioned space.
Wall Covering: Use of a non-permeable wall covering (some
paints, some wallpapers, and other types of coverings) which
severely restricts passage of air or water vapor can cause a
severe moisture problem. Typical results could be staining of
room surfaces, wall damage, as well as mold and mildew
growth in hot/humid climates.
Air Infiltration: Excessive air infiltration can magnify
problems associated with undersizing or oversizing of an
air conditioner unit and can be the root cause of insufficient
cooling, dehumidification, or heating. Some sources of air
infiltration include vents, gaps around windows and doors,
and improperly sealed floor, ceiling and wall joints.
Recommendation: For the above reasons it is strongly
recommended that a professional engineer be retained
to match the Zoneline unit with the building structure.
Air Distribution
Zoneline packaged terminal air conditioners and heat pumps
discharge air from the top of the unit through reversible
two-position discharge louvers. Unit discharge louvers are
reversed by removing the room cabinet from the unit,
removing seven screws that hold the louver section in
place, removing the louver section and rotating it end for
end, reinstalling the louver section in the room cabinet with
the seven screws, and reinstalling the room cabinet on the
unit. The unit is shipped from the factory with the discharge
louvers at an angle of 50° off vertical. In the alternate
position, the louvers will be at an angle of 40° off vertical.
All room cabinets return air through the front of the unit.
50°
40°
OVER 40 FT.
INCORRECT