Figure 9:
Removing valve
cap.
Maintenance And Service
the HI/LO knob by hand shown in Figure 9.
Figure 11: Flip
valve screw.
Red o-ring
is not visible
Red o-ring
is visible
LPG Configuration
b) Insert a
5
/32” or 4 mm Allen wrench into
the hexagonal key-way of the screw (see
Figure 10), rotate it counter-clockwise
until it is free and extract it.
c) Check that the screw is clean and if
necessary remove dirt.
d) Flip the screw (refer to Figure 11).
e) Using the Allen wrench as shown in
Figure 10, rotate the screw clockwise
Figure 12: O-ring on valve screw.
Loosen
Tighten
Figure 10: Removing
valve screw.
6. Convert the pilot injector:
a) Pull the pilot hood straight up to access
the pilot injector.
b) Using a
5
/32 or 4 mm Allen key,
remove the pilot injector.
c) Install the new pilot injector supplied
with this conversion kit. Simply screw
the new injector inside the pilot hood
using the Allen key,
d) Reinstall the hood by placing the hood
on the assembly, line up the key way,
and snap into place.
7. Convert the SIT gas valve:
a) Remove the black protection cap from
Figure 13. Ignitor
assembly beside the
burner.
until a torque of 9 inch lbs. WARNING! Do not over tighten the screw. It is
recommended that you grip the wrench by the short side.
f) Verify that if the conversion is from NG to LPG, the screw must be re-
assembled with the red o-ring visible (refer to Figure 12). If the conversion
is from LPG to NG, the red o-ring of the screw must be not visible.
g) Re-attach the black protection cap that was removed in step a (Figure 9).
8. Reinstall the burner, brick panels, log set, embers, and glass door. Also refer
to
Secondary inStallation - loG Set and eMberS inStallation. When re-installing the
burner, ensure that the burner to pilot hood relationship is similar to what is
shown in Figure 13. On some units you will need to pay special attention when
installing the burner that the venturi adjustment rod is properly installed into
the venturi adjustment piece welded to the burner venturi tube
9. Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the
unit.
10. Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap
and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by
using an approved pipe thread sealant or approved Teon tape. NEVER USE AN OPEN FLAME WHEN
TESTING FOR LEAKS.
11. Reconnect the electrical power to the unit.
12. Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition and
operation and proper ame appearance. Also refer to
Secondary inStallation - loG Set and eMberS
inStallation for a ame appearance picture.
13. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the
unit has been converted to a different fuel type.