Setup Menu
Liebert
®
AC4
™
76
Restart Delay
For details on this feature, see 7.8.5 - Specify Restart Time.
A.6.7 Override Output
For details on this feature, see 7.9 - Override Output.
Setup Operation - Restart Delay
SETUP OPERATION
Select operation to edit
OPERATION STATE
1=AUTO SEQUENCING OFF
2=STANDBY TESTING OFF
3=FAILED STANDBY N
4=HOLD DELAY 10:00
5=RESTART DELAY 00:06
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:5
>DELAY BEFORE STARTUP UNIT(MM:SS)?
>[00:06]
>[
>COMMAND SUCCESSFUL
Override Output
OVERRIDE OUTPUT
Manually override
an output point
Select output to override
OUTPUT CONTROL
1=DEVICE_1 AUTO ********************************
2=DEVICE_2 AUTO AUTO = CONTROL BY PANEL
3=DEVICE_3 FORCE ON FORCE ON = FORCE ON BY OPERATOR
4=DEVICE_4 FORCE ON FORCE OFF= FORCE OFF BY OPERATOR
5=RETURN TO SETUP MENU ********************************
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
>OVERRIDE OUTPUT DEVICE_1-AUTO(2),FORCE ON(1),FORCE OFF(0).
>[2]
>[
>COMMAND SUCCESSFUL