Emerson AC4 Home Security System User Manual


 
Setup Menu
75 Liebert
®
AC4
Failed Standby
For details on this feature, see 7.8.3 - Specify Failed Standby Response.
Hold Delay
For details on this feature, see 7.8.4 - Specify Hold Delay Time.
Setup Operation - Failed Standby
SETUP OPERATION
Select operation to edit
OPERATION STATE
1=AUTO SEQUENCING OFF
2=STANDBY TESTING OFF
3=FAILED STANDBY N
4=HOLD DELAY 10:00
5=RESTART DELAY 00:06
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:3
>IF FAILED STANDBY,IN SAME FAILED ZONE, ENABLE A DISABLED UNIT-YES(Y) OR NO(N)?
>[N]
>[Y]
>COMMAND SUCCESSFUL
Setup Operation - Hold Delay
SETUP OPERATION
Select operation to edit
OPERATION STATE
1=AUTO SEQUENCING OFF
2=STANDBY TESTING OFF
3=FAILED STANDBY N
4=HOLD DELAY 10:00
5=RESTART DELAY 00:06
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:4
>HOLD DELAY (MM:SS)
>[10:00]
>[
>COMMAND SUCCESSFUL