Emerson 54ea Pet Fence User Manual


 
MODEL 54eA SECTION 5.0
SOFTWARE CONFIGURATION
5.5 CHOOSING DISPLAY OPTIONS (CONTINUED)
8. Set the remainder of the display parameters. Use the and keys
to choose the desired parameter. Then press Edit (F4). Use the
key to move the cursor to the desired selection. Press Save (F4) to
store.
SECURITY CAUTION
The controller uses the timeout value to activate security. Once
the controller is unlocked by entering a security code, security will
not re-activate until a display timeout occurs. If timeout has been
turned off, security will never reactivate.
Temp units: °C
Output 1: mA
Output 2: mA
Exit Edit
Language: English
Display left: I
Display right: Out 2
Exit Edit
Display contrast: 40
Timeout: On
Timeout value: 10 min
Exit Edit
Temp units °C or °F
Output 1 mA or % of full scale
Output 2 mA or % of full scale
Language English, Français, Español, Deutsch, Italiano
Display left sensor current (I), pH (appears only if free chlorine
is being measured and pH was enabled), alarm 1
setpoint (no units), alarm 3 setpoint (no units),
or blank
Display right sensor current (I), pH (appears only if free chlorine
is being measured and pH was enabled), alarm 2
setpoint (no units), alarm 3 setpoint (no units),
output 2, or blank
Display Contrast 00 (lightest)-99 (darkest); the display contrast
changes as the number changes
Timeout Timeout returns the display from any other screen
to the main display if no key is pressed before the
timeout value is exceeded.
Polling address Identifies controller in multi-drop HART applications.
Timeout value
29