Emerson 308014EN Water Heater User Manual


 
2-7
Rosemount Tank Radar REX
Chapter 2 Safety
Installation Manual
308014EN, Edition 4
May 2013
2.3.5 FF Adaptor Card (FFA)
Figure 2-5. Certification label for the FF Adaptor Card (FFA).
The FF Adaptor card (FFA) is mounted within the flameproof enclosure.
It is, in conjunction with a Fieldbus Communication Board
(BAS01ATEX1385U), used to interface to an intrinsically safe Fieldbus.
The following information is provided as part of the label of the FFA:
Name and address of the manufacturer
(Rosemount Tank Radar AB)
CE Conformity Marking:
Year of construction
Marking for explosion protection:
[Ex ia] IIC (Ga) (-40 °C Ta +85 °C)
Baseefa(2001) ATEX EC-Type Examination Certificate number:
Baseefa04ATEX0119U
Schedule of Limitations
The FF Adaptor Card must be housed within an enclosure which
provides a degree of protection of at least IP20. If the FF Adaptor
Card is mounted within a hazardous area it must be installed
within an appropriately certified flameproof enclosure.
The arrangements for the connections to non-hazardous area and
hazardous area external circuits must comply with the require-
ments of Clause 6.3 of EN 50020:2002.
The FF Adaptor Card is considered to be suitable for use within
EEx d apparatus with an Ambient Temperature range of
(-40 °C Ta +85 °C).
Note! For electrical (I.S.) parameters refer to the appended EC-Type
Examination Certificate Baseefa04ATEX0119U.