DVS -30-2 Indoor Fireplace User Manual


 
Page 8 13369-1-0203
MANTEL
MANTEL
4" (102mm)
4" (102mm)
2 1/2"(64mm)
2 1/2"(64mm)
10 1/2"
10 1/2"
(267mm)
12"
(305mm)
TOP EDGE OF FIREPLACE
TOP EDGE OF FIREPLACE
11 1/4"
11 1/4"
(286mm)
9 3/4"
9 3/4"
(248mm)
9"
(229mm)
6" (152mm)
6" (152mm)
10" (254mm)
10" (254mm)
8" (203mm)
8" (203mm)
12" (305mm)
12" (305mm)
12 3/4"
12 3/4"
(324mm)
LOCATING FIREPLACE
Figure 8
Note:** Island (C) and Room
Divider (D) installation is possible
as long as the horizontal portion of
the vent system (H) does not exceed
20 feet with a minimum vertical
run of 8 feet. See details in Venting
Section.
*When you install your Direct Vent
Fireplace in (D) Room divider or
(E) Flat on wall corner positions, a
minimum of 6 inches clearance
must be maintained from the
perpendicular wall and the front
edge of the appliance.
CLEARANCES
2" x 4" HEADER
2" x 4" HEADER
STAND OFF
STAND OFF
3" (76mm) HEIGHT
3" (76mm) HEIGHT
ABOVE TOPOF
FIREPLACE
GLASS FRONT
GLASS FRONT
TOP FRAMING
LEDGE
FINISHED WALL
FINISHED WALL
ADJUSTABLE
NAILING
FLANGES
SEE MANTLE CHART
SEE MANTLE CHART
FOR MAXIMUM MANTLE
FOR MAXIMUM MANTLE
DEPTH
SEE MANTLE CHART
SEE MANTLE CHART
FOR MINIMUM HEIGHT
FOR MINIMUM HEIGHT
OF MANTLEABOVE UNIT
OF MANTLEABOVE UNIT
CLEARANCE TO COMBUSTIBLES
BACK
0" (0 mm)
SIDE
0" (0 mm)
FLOOR
0” (O mm)
TOP STAND
OFF 0" (0 mm)
TOP FRAMING
LEDGE 0" (0 mm)
Figure 5
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the fireplace. The flow of heat can
ignite combustibles.
CLEARANCES TO COMBUSTIBLES
BACK SPACER 0" (0MM)
SIDE SPACER 0" (0MM)
FLOOR 0" (0MM)
TOP STAND OFF 0" (0MM)
TOP FRAMING LEDGE 0" (0MM)
Mantel Chart (Figure 6)
Figure 6
Clearances (Figure 7)
Clearance from top of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
Figure 7