DVS -30-2 Indoor Fireplace User Manual


 
13369-1-0203 Page 37
RF STANDING PILOT OPERATING INSTRUCTIONS
Features Benefits
Self powered millivolt receiver/valve No external power or batteries required to operate valve and flame modulation
Thermostat performance Flame cycles and modulates such that heat output equals heat loss from the room
Auto mode Flame & fan are controlled automatically
Self powered millivolt control No external power required to control gas valve and flame modulation
Integrated Valve Electronics No electronics, rheostat, or limit installation required
Failure analysis Troubleshooting with information from LED
Pilotstat interlock When valve is turned off, power unit must drop out before pilot can be relit
F or C temperature units Display local temperature units
Functions
Flame powered system
Flame powered flame modulation
Electronics integrated into valve to provide thermostat, flame, and fan functions with RF commands
Temperature compensated RF receiver
Main burner goes to "high" when manual switch is set on "local"
Fan powered by 120 vac
Transmitter Signal
When the transmitter is in the Auto mode, a signal is sent every 10 minutes if there is a change in the room temperature
When the transmitter is in the On or Off modes, a signal is also sent every 10 minutes with the status of On or Off condition
The transmitter will work at a minimum of 25 feet from the receiver
Make sure antennae is not touching metal and is horizontal. Refer to Figure 54.
Receiver Shutdown of Burner
In the remote, auto mode the valve shuts off if it does not receive a signal within 3 hours from the transmitter
In the local mode the valve does not shut off
In the remote, manual mode the vavle shuts off if it does not receive a signal within 6 hours from the transmitter
Thermopiles
The negative leads (white) must be connected to the terminals with the one white dot marked next to them
Each thermopile must provide at least 500 mV open circuit voltage
If output is erratic, check thermopile for intermittent shorts
LED Troubleshooting
Note: In normal operation, LED blinks once every two seconds; also, LED will be on for one second after every valid command
received by the RV8310D; these are not error codes.
Failure codes (see Table) can occur anytime after the pilot burner is lit. Failure code timing is 1/4 second on, 1/2 second off.
Sequence is failure code followed by LED not blinking for four seconds.
In the event of multiple failure codes, the next failure code follows the previous failure code by approximately three seconds.
Code Service Action
8 Replace valve
7 Confirm stepper motor connection exists
4 Fuel conversion plug missing or has poor connection (RV8310E only)
3 Replace thermopile with Q313
2 Device too hot. Check application
1 None required. This is normal operation and indicates the control is powered.
For additional Standing Pilot Troubleshooting refer to Page 30.