VENTING INSTALLATION
INSTRUCTIONS
WARNING: Read all instruc-

  
Failure to do so could result in


WARNING: Seal all connec-
   
silicone every time a vent con-

  
   
sealant to the male end of the

-
seal any connections after main-

NOTICE: Failure to follow these in-

NOTICE: Do not seal termination

   

INSTALLATION
Consult local building codes before beginning the
installation. The installer must make sure to select
the proper vent system for installation. Before
installing vent kit, the installer must read this
replace manual and vent kit instructions.
Only a qualied service person should install
venting system. The installer must follow these
safety rules:
Wear gloves and safety glasses for protection
Use extreme caution when using ladders or
when on roof tops
Be aware of electrical wiring locations in walls
and ceilings
The following actions will void the warranty on
your venting system:
Installation of any damaged venting component
Unauthorized modication of the venting sys-
tem (Do not cut or alter vent components)
Installation of any component part not manu-
factured or approved by DESA
Installation other than as instructed by these
instructions






   



There are two basic types of direct-vent installation:
Horizontal Termination
Vertical Termination
It is important to select the proper length of vent
pipe for the type of termination you choose. It is
also important to note the wall thickness.
For Horizontal Termination: Select the amount of
vertical rise desired. The horizontal run of venting
must have 1/4" rise for every 12" of run towards
the termination.
WARNING: Never run the
vent downward as this may


You may use one or two 90° elbows in this vent
conguration. See Horizontal Termination Con-
gurations on page 13.
For Vertical Termination: Measure the distance
from the replace ue outlet to the ceiling. Add
the ceiling thickness, the vertical rise in an attic or
second story, and allow for sufcient vent height
above the roof line. You may use one or two 90°
elbows in this vent conguration. See Vertical
Termination Congurations on page 16.
Note: You may use two 45° elbows in place of a
90° elbow. You must follow rise to run ratios when
using 45° elbows.
For two-story applications, restops are required at
each oor level. If an offset is needed in the attic,
additional pipe and elbows will be required.
You may use a chase with a vent termination with
exposed pipe on the exterior of the house. See In-
stalling Vent System in a Chase, page 11.