FIREPLACE INSTALLATION
Continued
We recommend that you install a sediment trap/
drip leg in supply line as shown in Figure 23. Lo-
cate sediment trap/drip leg where it is within reach
for cleaning. Install in piping system between fuel
supply and replace. Locate sediment trap/drip leg
where trapped matter is not likely to freeze. A sedi-
ment trap traps moisture and contaminants. This
keeps them from going into replace gas controls.
If sediment trap/drip leg is not installed or is in-
stalled wrong, replace may not run properly.
Figure 23 - Gas Connection
CSA Design-Certied
Equipment Shutoff Valve
with 1/8" NPT Tap*
3" Minimum
Approved
Flexible
Gas Line
Cap Pipe Tee Joint
Nipple
Sediment Trap/Drip Leg
Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
Propane/LP From
External Regulator
(11" W.C. to 14"
W.C. Pressure)
* The CSA design-certied equipment shutoff
valve may be supplied with the appliance or you
can purchase it from your retailer.
CONNECTING FIREPLACE TO GAS
SUPPLY
Installation Items Needed
3/4" and a 7/8" open end wrench or adjustable
wrench
sealant (resistant to propane/LP gas, not pro-
vided)
1. Remove lower louver door panel by lifting
up until disengaged. Swing forward and out
of locating slots at bottom.
2. Route exible gas line (provided by installer)
from equipment shutoff valve to replace.
Route exible gas supply line through one of
the access holes on each side of the replace
cabinet.
3. Attach exible gas line from gas supply to the
1/2" are tting provided on the control valve
(see Figure 24).
4. Check all gas connections for leaks (see
Checking Gas Connections).
Figure 24 - Connecting Flexible Gas Line
to Millivolt Valve
Flexible Gas Line
Do NOT Kink
Equipment
Shutoff Valve
To Gas Supply
(Natural)
To External
Regulator
(Propane/LP)
Control Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an open
ame to check for a leak. Apply
noncorrosive leak detection uid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect replace and its individual equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig (3.5 kPa)
will damage replace gas regulator.
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas replace or opening main gas
valve located on or near gas meter for natural
gas replace or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection uid to all
joints. Bubbles forming show a leak. Correct
all leaks at once.
5. Reconnect replace and equipment shutoff
valve to gas supply. Check reconnected ttings
for leaks.