Crestron electronic GLPS-HSW Indoor Furnishings User Manual


 
Green Light Power Switching Crestron Commercial Lighting Design Guide
Doc.4775A 18
Support Services for 400A feed and other main circuit
breaker options.
Number of Circuits: Choose one of the following numeric
values from the appropriate column to specify the number of
controlled circuits in
the panel:
Note: Small, Medium, and Large refer to the default
panel size per number of circuits. Consult Crestron Sales
Support Services for alternate configurations.
Voltage: To specify the circuit breaker voltage, enter 120
for 120/208V or 277 for 277/480V.
AIC Rating: Choose one of the following values from the
appropriate column to specify the Ampere Interrupting
Capacity of the circuit breakers:
Note: Consult Crestron Sales Support Services MCB options.
Door OptionEnter ND to omit the local control access
door. (The circuit breaker door cannot be omitted.)
GLPS-SW-MLO GLPS-SW-MCB
Small: 10, 16 10, 15
Medium: 20, 26, 30 20, 26, 27
Large: 32, 36, 40, 42 32, 36, 39
120 Volt 277 Volt (
10K 18K
22K 35K
65K 65K