Crestron Commercial Lighting Design Guide Green Light Power Switching
Doc 4775A 15
Feed Type: Choose one of the following to specify the type of
feed:
MLO Main lug only
MCB60 60A back-fed main circuit breaker
MCB80 80A back-fed main circuit breaker
MCB100 100A back-fed main circuit breaker
MCB125 125A back-fed main circuit breaker
(available for 277V only)
Note: Main feeds are 3-phase, 4-wire; rated 225A @ 120/208V
or250A @ 277/480V. Consult Crestron Sales Support Services for
400Afeed and other main circuit breaker options.
Number of Circuits: choose one of the following numeric
values from the appropriate column to specify the number
of controlled circuits in the panel:
Note: Small, Medium, Large and Extra Large refer
to the default panel size per number of circuits. Consult
Crestron Sales Support Services for alternate configurations.
Voltage: To specify the circuit breaker voltage, enter 120
for 120/208V or 277 for 277/480V.
AIC Rating: Choose one of the following values from the
appropriate column to specify the Ampere Interrupting
Capacity of the circuit breakers:
Note: Consult Crestron Sales Support MCB options.
Door OptionEnter ND to omit the local control access
door. (The circuit breaker door cannot be omitted).
GLPS-HSW-MLO GLPS-HSW-MCB
Small: 8, 12 8, 12
Medium: 16, 20, 24, 28, 30 16, 20, 24, 27, 30
Large: 32 32
Extra Large: 36, 40, 42 36, 39
120 Volt 277 Volt
10K 18K
22K 35K
65K 65K