Crestron electronic GLPS-HSW Indoor Furnishings User Manual


 
Crestron Commercial Lighting Design Guide Green Light Power Switching
Doc 4775A 13
Crestron Green Light Power Switching Panels are available in five basic configurations. Use to the following cross-reference table to
begin specifying the configuration that fits your application.
This table represents the full line of Crestron Green Light and Green Light Express Power Switching panels, as well as Green Light
and Green Light Express Architectural Dimming panels. All are shown side-by-side for easy comparison. The Power Switching panels
are each fully detailed under their respective specifications pages within this document. For details about Architectural Dimming
panels, please refer to the Crestron Green Light Architectural Dimming Specification Guide, Doc. 4785 (future).
GREEN LIGHT GREEN LIGHT EXPRESS
Power Switching Architectural Dimming Power Switching Architectural Dimming
GLPS-HSW
GLPS-SW
GLPD-DIM
GLPS-HSW-FT
GLPS-SW-FT
GLPS-HDSW-
FT
GLPD-DIM-FT
GLPD-DIMX-FT
Switching Relay Types
A
rcless High-inrush
Standard high-inrush
Modular high-inrush
2-pole available
Dimming Load Types
Incandescent, MLV
ELV
2-wire fluorescent
3-wire fluorescent
0-10V fluorescent
Ratings
Voltages
120/230/277 120/230/277 120/230/277 120/230/277 120/230/277
120/230/
277/347
120/230/277 120/230/277
Output capacity lighting
loads
16A 16A 16A
4
16A 16A 20A 16A
4
8A
Output capacity, motor
loads@ 120/230/277 volts
0.5/1/1 hp 1/2/2 hp 0.5/1/1 hp 0.5/1/1 hp 1/2/2 hp
0.5/1.5/1.5
hp
0.5/1/1 hp
Rated relay lifetime
5
1,000,000 10,000 1,000,000 1,000,000 10,000 30,000 1,000,000
Circuit Breakers
Integrated branch breakers
A
vailable main breake
r
Additional Features
Load state indicators
Local override
Emergency override
Mechanical override
Local control access door
option
Backup power supply
capable
Notes:
1.Please see Crestron Green Light Architectural Dimming Specification Guide, Doc. 4785 (future) for full description and specifications.
2. Supported via use of appropriate CLS-EXP expansion module.
3. 3-wire fluorescent loads require 2 control outputs per load.
4. Consult detailed specifications for ratings for ELV loads.
5. Relay lifetime based on number of cycles (on/off) with full electronic ballast load.